4.4 Pre-Heating function
This function is active only if automatic heating mode
has been selected.
When set to Automatic, the function anticipates the
heating system start time (not before 00:00 of the
same day) so that the room temperature set by the user
is reached at the start of the programmed band. The
REMOTE calculates a hypothetical first Pre-activation
time: if the programmed room temperature is reached
in a shorter time than that calculated, the Pre-Heating
time will be decreased and vice versa. In this way
self-learning is created, for determining the shortest
Pre-activation time necessary.
The REMOTE also offers the possibility of setting a fixed
Pre-Heating ramp: in this case the room temperature
will be raised by 3°C an hour.
_________________________________________________________________________________________________________________________________________________
During the pre-heating function, the room temperature °C symbol blinks.
The pre-heating function ends when the difference between the programmed and actual room temperature is
less than 0.5 °C.
It is therefore important that the automatic heating
program be programmed according to the desired
time when heat is required and not the desired heating
system start time.
Follow the instructions below to activate or deactivate
this function.
1. Press the button for 3 seconds.
2. The display shows parameter CU.
3. Press the button repeatedly until parameter P2 is
4. Press any other button to exit the menu.
code 3542A980 - Rev. 00 - 01/2022
displayed.
Set to 0 using the buttons
Pre-Heating. Set to 1 using the buttons
to activate Automatic Pre-Heating. Set to 2 using the
buttons
/
to activate Pre-Heating with
fixed ramp of 3°C per hour.
/
to deactivate
/