The module uses four addresses: The configured address plus
the next three numbers (for example,. 201, 202 and 203 if the
configured address is 200).
Status LED
The status LED is lit constantly during alarm.
Maintenance and testing
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
To test the module:
1.
Configure the module as an output to be activated by a
detector or manual call point.
2.
Activate a detector or manual call point associated with
the module.
3.
If the status LED and control panel fail to indicate the test
all connections should be checked and the module
address verified.
Specifications
Operating voltage
Loop current consumption:
at 24 VDC (standby)
at 35 VDC (standby)
Alarm
Current consumption:
24 VDC aux. supply (standby)*
24 VDC aux. supply (alarm)*
Relay contact rating
Operating temperature
Storage temperature
Relative humidity
Weight
Dimensions
* Excluding loop devices
Regulatory information
This section provides a summary on the declared performance
according to the Construction Products Regulation
(EU) 305/2011 and Delegated Regulations (EU) 157/2014 and
(EU) 574/2014.
For detailed information, see the product Declaration of
Performance (available at firesecurityproducts.com).
Certification
Certification body
0370
Declaration of
360-4109-0899
Performance number
Year of first CE marking
08
Product identification
KAL734C
Intended use
See the product Declaration of Performance
Declared performance
See the product Declaration of Performance
2 / 16
22 to 38 VDC
110 µA
135 µA
<10 mA
100 µA
<10 mA
30 VDC / 0.5 A or
50 VAC / 0.5 A
−10 to +50ºC
−10 to +70ºC
10 to 95% (noncondensing)
835 g
223 × 173 × 80 mm
Manufacturer
Carrier Manufacturing Poland Spòlka Z o.o.
Ul. Kolejowa 24. 39-100 Ropczyce, Poland.
Authorized EU manufacturing
representative: Carrier Fire & Security B.V.,
Kelvinstraat 7, 6003 DH Weert, Netherlands
2012/19/EU (WEEE directive): Products
marked with this symbol cannot be
disposed of as unsorted municipal waste in
the European Union. For proper recycling,
return this product to your local supplier
upon the purchase of equivalent new
equipment, or dispose of it at designated
collection points. For more information see:
recyclethis.info.
Contact information and product
documentation
For contact information or to download the latest product
documentation, visit firesecurityproducts.com.
Product warnings and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE TO AND
INSTALLATION BY QUALIFIED PROFESSIONALS.
CARRIER FIRE & SECURITY B.V. CANNOT PROVIDE ANY
ASSURANCE THAT ANY PERSON OR ENTITY BUYING ITS
PRODUCTS, INCLUDING ANY "AUTHORIZED DEALER" OR
"AUTHORIZED RESELLER", IS PROPERLY TRAINED OR
EXPERIENCED TO CORRECTLY INSTALL FIRE AND
SECURITY RELATED PRODUCTS.
For more information on warranty disclaimers
and product safety information, please check
https://firesecurityproducts.com/policy/product-
warning/ or scan the QR code:
ES: Instrucciónes de instalación
Descripción
El módulo KAL734C proporciona cuatro salidas de relé libre de
potencial al bucle del sistema de incendios. Cada relé permite
la instalación de contactos comunes (C), normalmente abiertos
(NA) y normalmente cerrados (NC).
El módulo puede utilizarse con cualquier dispositivo y la opción
de contacto utilizada establecerá el evento deseado.
Instalación
Precaución:
Consulte el estándar EN 54:14 y las normativas
locales para obtener información acerca de las directrices de
planificación, diseño, instalación, funcionamiento, utilización y
mantenimiento del sistema.
Instalación del módulo
Desconecte la fuente de alimentación del sistema de incendios
e instale el módulo en la carcasa protectora proporcionada.
Conecte el hilo apantallado del cable de bucle al tornillo de
tierra.
P/N 10-5151-501-104-02 • ISS 09JUN21