Communicator Troubles Displayed On A Pc1616/1832/1864; Installing Tl265 Communicator; Installing Tl265 Communicator With Alexor Pc9155; Alexor Pc9155 Panel Programming - DSC TL260 Manual De Instrucciones

Comunicador de alarma vía ethernet/internet
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Network Connection
Use only CAT 5 cable. Supervised
Input Ratings (from Bell + and Bell -)
11.1V - 12.6 V
DC:
DSC Panel minimum power requirements
16 V
40 VA transformer; 12 V
AC
If external bell/siren is not used, install 1K ohm ½W 5%
between the Bell + and Bell - terminals on panel.
AUX+
AC AC
AUX-

Communicator Troubles displayed on a PC1616/1832/1864

General System trouble is the only trouble that will appear on the keypad Liquid Crystal Display (LCD) when encountered by a
Communicator installed in a PC1616/1832/1864 panel. Enter [*][2] on the panel, the trouble light will indicate 3 flashes for Gen-
eral System Trouble. Log entry will show Fault or Restore for each of the following events.
• T-Link Network Fault/Restore: This log will occur for Ethernet Trouble or when trouble restores.
• T-Link Receiver Trouble/Restore: This log will occur for the following trouble conditions: Receiver Not Available Trouble, Receiver Super-
vision Trouble, or FTC Trouble, or when each of the trouble conditions is restored.
• T-Link Comm. Fault/Restore: This log will occur when the panel loses/regains communications with the Communicator.
Refer to the T-Link Installation Manual if additional troubleshooting information is required for these faults.
I

Installing TL265 Communicator with ALEXOR PC9155

1. Remove the front cover of the PC9155 Panel and disconnect AC power and battery+ (red) connector from battery.
2. Hold the Communicator module with the RJ45 connector at bottom left. Tilt module down slightly to right and align the hole with the bot-
tom right panel tab and the two slots on the right side. Gently press the communicator into the slots, then press down on left to lock it in
position, ensuring the tab at top of panel aligns with the hole on Communicator. (See Figure 4).
3. Connect the PC-LINK connector. Red wire on pin 5 (bottom) on the panel and the communicator. (See Figure 5).
4. Connect the Ethernet plug to the RJ45 connector on Communicator. If a shielded CAT 5 cable is used, a jumper may be placed between
the GND and SHLD connections of the Communicator 2-terminal block (left of RJ45 jack) to reduce signal noise.
NOTE: Do not attach this jumper if the Ethernet cable shield is grounded by the equipment at the other end.
5. Reconnect the battery + connector to the panel then the AC power. (the Communicator and Panel will power up together).
a. Observe that the Communicator's red and yellow LEDs are flashing together while it initializes. The red and yellow LEDs will continue
to flash until the unit has successfully communicated to all programmed receivers.
b. Observe that the yellow Ethernet Link LED (to right of RJ45 connector) is ON. See Figure 5.
NOTE: Initialization may take several minutes. Do not leave the installation until the red and yellow LEDs have stopped flashing.

ALEXOR PC9155 Panel Programming

1. Establishing a communication channel between the Communicator and the panel is critical to ensuring the desired operation of the two
units. The following must be completed during the on-site installation. Program the following at the panel to ensure that the Communica-
tor and the panel will work together as intended. Panel Sections must be programmed at the panel keypad. Enter [*][8][Installer Code]
[Section Number] for panel programming. Record any values that are modified from their default, in the appropriate Programming
Worksheets for the Panel and Communicator.
PC1616/1832/1864
UA503
100mA Standby ; 400mA Alarm
7Ah battery
DC
BELL+
PGM1
PGM3
RED BLK YEL GRN
Z1 COM Z2
BELL-
PGM2
PGM4

INSTALLING TL265 COMMUNICATOR

Figure 3 Communicator wiring diagram
Hardware
Default
Jumper
PWR PWR GND GND
Red
1
RING
EGND
Z3 COM Z4
Z5 COM Z6
Z7 COM Z8
4
TL260
Network Link
(Yellow LED)
Red
PC-LINK
1
GND
SHLD
CON 4
PC-LINK
R-1
TIP
T-1
Ethernet
CAT 5 with
RJ45 plug
+
-
External

Hide quick links:

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Tl265

Tabla de contenido