Descargar Imprimir esta página

Sime MURELLE HE 110 R ErP Manual De Instrucciones página 66

Ocultar thumbs Ver también para MURELLE HE 110 R ErP:

Publicidad

Idiomas disponibles

Idiomas disponibles

Type B
KEY
1
90° MF polypropylene curve (6 pcs.) code 8077450
2 a Polypropylene extension L. 1000 (6 pcs.) code 8077351
2 b Polypropylene extension L. 500 (6 pcs.) code. 8077350
3
Hinged tile code 8091300
4
Roof terminal kit L. 1381 code 8091204
STAFFA TELAIO
CALDAIA
5
Polypropylene extension L. 250 with socket code 6296513
6
45° MF polypropylene curve (6 pcs.) code 8077451
7
Exhaust terminal code 8089501
8
Internal-external ring nut kit code 8091500
11
Rubber gasket ø 80 (supplied as standard)
66
G
M
R
Pmin
ø 80 ACCESSORY LOAD LOSS TABLE
Accessory ø 80
90° MF polypropylene curve
45° MF polypropylene curve
Polypropylene extension L. 1000
Polypropylene extension L. 500
Roof exit terminal L. 1381
Exhaust terminal
Polypropylene extension L. 250 with socket
When load loss of the individual accessories connected
exceeds 4 mm H
O, in order to assure the correct
2
operation of the appliance, set the installer parameter
PAR 9 as indicated in TABLE 1 (see point 3.3 to access
the installer parameters).
TABLE 1
Load loss
(mm H
O)
2
0 - 4
4 - 8
8 - 12
12 - 16
16 - 20
20 - 24
24 - 28
28 - 32
32 - 36
36 - 40
40 - 42
WARNING:
Before installing accessories, lubricate the
internal part of gaskets with silicon-based
products. Avoid using oils and greases.
Pmax
Load loss
(mm H
O)
2
3,5
2,3
1,4
0,7
5,0
4,0
0,3
WARNING !
PAR 9
(long chimneys)
0
1
2
3
4
5
6
7
8
9
10
Fig. 6

Publicidad

loading