Descargar Imprimir esta página

Sime MURELLE HE 110 R ErP Manual De Instrucciones página 76

Ocultar thumbs Ver también para MURELLE HE 110 R ErP:

Publicidad

Idiomas disponibles

Idiomas disponibles

replaced. The electronic board is faul-
ty.
In the case of a sudden lack of voltage, the
burner will immediately switch off. When
voltage returns, the boiler will automati-
cally start up again.
1200
1000
800
600
400
200
0
0
250
500
Flow Rate (l/h)
0
400
Residual head (mbar)
1011
1004
Fault finding
Fault
1.
Pump is not running. No
power supply.
2.
Pump is not running. Normal
power supply.
3.
Pump runs at maximum
speed and cannot be
controlled.
4.
Noise in the system.
5.
Noise in the pump.
6.
Insufficient flow.
76
3.8
HEAD AVAILABLE
TO SYSTEM (fig. 14)
Residual head for the heating system is
shown as a function of rate of flow in the
graph in fig. 14.
The speed of the modulating pump system
750
1000
1250
1500
1750
2000
800
1200
1600
2000
2400
2800
998
981
947
916
843
722
Cause
• System is switched off.
• A fuse in the installation is blown.
• The circuit breaker has tripped.
• Power supply failure.
• Controller is switched off.
• Pump is blocked by impurities.
• Pump is defective.
• No signal from signal cable.
• There is air in the system.
• Differential pressure is too high.
• There is air in the pump.
• Inlet pressure is too low.
• Pump performance is too low.
• Hydraulic system is closed or system pressure is
insufficient.
2250
2500
2750
3000
3250
FLOW RATE (l/h)
3200
3600
4000
4400
4600
590
477
348
233
172
Remedy
Check the system controller.
Replace the fuse.
Check the power connection and switch on the circuit
breaker.
Check the power supply.
Check the controller and its settings.
Remove impurities. Unscrew the deblocking screw at the
front of the pump. Deblock the pump from the front of the
control box with a screwdriver. Be aware of splashing hot
water.
Replace the pump.
Check if the cable is connected to the controller. If it is,
replace the cable.
Vent the system.
Reduce the pump performance at the pump or external
controller.
Let the pump run. The pump vents itself over time.
Increase the system pressure or check the air volume in
the expansion tank, if installed.
Check the external controller and the pump settings.
Check the non-return valve and filter. Increase the
system pressure.
is set as default (installation parameter
PAR 13 = Au).
3500
3750
4000
4250
4500
4750
5000

Publicidad

loading