4.8 Language choice
4.9 Switching points
1=>2
adjustment range: 10 ... 160 l/min
factory setting: 23 l/min
2=>3
adjustment range: 10 ... 160 l/min
factory setting: 46 l/min
3=>4
adjustment range: 10 ... 160 l/min
factory setting: 69 l/min
2=>1
adjustment range: 10 ... 160 l/min
factory setting: 16 l/min
3=>2
adjustment range: 10 ... 160 l/min
factory setting: 34 l/min
4=>3
adjustment range: 10 ... 160 l/min
factory setting: 54 l/min
4.10
Factory settings
Different languages are available in the „Settings/Language"
menu.
• English
• German
• French
• Spanish
• Italien
Whether a module is switched on or off depends on the draw
off rate. Each stage (number of modules) is characterised by
a switch-on threshold and a switch-off threshold. The switch-
on and switch-off thresholds for the switching points can be
adjusted in the „Settings/Switching p." menu.
Switching point for switching from operation with 1 module
to operation with 2 modules.
Switching point for switching from operation with 2 modules
to operation with 3 modules.
Switching point for switching from operation with 3 modules
to operation with 4 modules
Switching point for switching operation with 2 modules to
operation with 1 module
Switching point for switching from operation with 3 modules
to operation with 2 modules.
Switching point for switching from operation with 4 modules
to operation with 3 modules.
Note:
The minimum difference between switch-on and switch-off
threshold must be 3 l/min. The minimum difference between
two stages (switch-on condition) must be 10 l/min.
All values can be set back to the factory settings in the
„Settings/Factory settings" menu.
• Select „Factory settings" in order to set back all values to
the factory settings.