FriwaMaster
5.
Overview of functions and option
Menu
MEas. values:
Domestic hot water temperature
T-DHW
Draw off rate
Draw
Operating state module 1 ... 4
Module 1 ... 4
Operating state error relay
Error Rel.
Operating state return connection
Ret. Con.
Return temperature
T-R
Store temperature
T-ST
Temperature at sensors 1-6
S1 ... S6
Reports:
Normal operation
Everything OK
Relay - manual operation
-Manual Operat.
Draw off sensor defective
!Draw se. def.
Return sensor defective
!T-R deffect.
Store sensor defective
!T-Sp defect
Storage module defective
!EEProm
Software version
SW-Version
Balance Values:
Operating days
Operat. Days
Maximum draw of rate
Draw
Minimum domestic hot water temperature
DHW min
Maximum domestic hot water temperature
DHW max
Minimum return temperature
R min
Maximum return temperature
R max
Minimum store temperature
ST min
Maximum store temperature
ST max
Operating time return valve
Ret. Con.
Operating time - valve - module 1 ... 4
Modul 1 ... 4
Manual operation menu
Manual Operation
Valve mode fo modules 1 ... 4
Module 1 ... 4
Mode of return valve
Ret. Con.
Mode of error relay
Error Rel.
Settings:
Module 1 ... 4 option
Module 1 ... 4
Selection of function - relais 5
Fnc. R5
Switch-on difference return valve
DT R on
Switch-off difference return valve
Dt R off
Time
Time
Language choice
Language
Switching points for switching on and off
-switching p.-
individual modules
Reset of all values to factory settings
Factory settings
28
|
Description
Range
Factory setting
0 ... 100 °C
0 ... 12000 l/h
Off / On
Off / On
Bottom / Top
-30 ... 250 °C
-30 ... 250 °C
-30 ... 250 °C
0 ... 99999.
0 ... 12000 l/h
0 ... 100 °C
0 ... 100 °C
-30 ... 250 °C
-30 ... 250 °C
-30 ... 250 °C
-30 ... 250 °C
0 ... 99999 h
0 ... 99999 h
Off / Auto / On
Bottom / Auto / Top
Off / Auto / On
Yes / No
None / Error relay /
Return connection
0 ... 25 K
0 ... 25 K
-----
0
0
100 °C
0 °C
250 °C
-30 °C
250 °C
-30 °C
0
0
-----
Auto
Auto
Auto
Yes
Non
5,0 K
3,0 K