Descargar Imprimir esta página

Saivod SAP723 Manual Del Usuario página 124

Publicidad

Idiomas disponibles

Idiomas disponibles

Purge the refrigerant circuit with nitrogen for 5 min.
Evacuate again.
Remove parts to be replaced by cutting, not by flame.
Purge the braze point with nitrogen during the brazing
procedure.
Carry out a leak test before charging with refrigerant.
Reassemble sealed enclosures accurately. If seals are
worn, replace them.
Check safety equipment before putting into service.
d) Decommissioning
If the safety is affected when the equipment is putted
out of service, the refrigerant charge shall be removed
before decommissioning.
Ensure sufficient ventilation at the equipment location.
Be aware that malfunction of the equipment may be
caused by refrigerant loss and a refrigerant leak is pos-
sible.
Discharge capacitors in a way that won't cause any spark.
Remove the refrigerant. If the recovery is not required by
national regulations, drain the refrigerant to the outside.
Take care that the drained refrigerant will not cause any
danger. In doubt, one person should guard the outlet.
Take special care that drained refrigerant will not float
back into the building.
Evacuate the refrigerant circuit.
Purge the refrigerant circuit with nitrogen for 5 min.
Evacuate again.
Fill with nitrogen up to atmospheric pressure.
Put a label on the equipment that the refrigerant is re-
moved.
e) Disposal
124

Publicidad

loading