Descargar Imprimir esta página

Eaton DIN24240DC Manual De Instrucciones página 16

Ocultar thumbs Ver también para DIN24240DC:

Publicidad

Idiomas disponibles

Idiomas disponibles

C C h h a a p p t t e e r r 5 5 O O p p e e r r a a t t i i o o n n
5 5 . . 1 1
S S t t a a r r t t u u p p a a n n d d N N o o r r m m a a l l O O p p e e r r a a t t i i o o n n
To Start the UPS:
1.
Ensure that the UPS input and output wiring are connected and that the correct voltage is being supplied
to the UPS. See
2.
Verify that the external batteries are connected. See
3.
Press the power ON/OFF button on the front of the UPS for three seconds.
4.
Verify that the green power LED illuminates solid indicating the UPS is operating normally and any loads
are powered and protected.
5.
Check the UPS front panel to verify that there are no active faults. Do not proceed until all active faults are
cleared see
5 5 . . 2 2
U U P P S S S S h h u u t t d d o o w w n n
To shut down the UPS:
1.
Press and hold the UPS ON/OFF button for three seconds. The UPS then transfers to the OFF mode and
the green power LED turns off.
If you are planning on removing the UPS or EBM (if applicable) from the DIN rail ensure all sources of DC power
have been disconnected and properly isolated.
5 5 . . 3 3
B B a a t t t t e e r r y y M M o o d d e e
When the UPS is operating on battery mode the green power indicator will flash once per second. Once the
battery capacity reaches the low battery the green power indicator will flash every 0.3 seconds.
5 5 . . 4 4
U U P P S S S S e e l l f f T T e e s s t t
The UPS self test feature is preformed automatically when the UPS has access to acceptable line voltage. If
the battery voltage is less than 10VDC the unit will consider the battery as abnormal and fail the test. If the
battery voltage is above 10VDC the UPS will initiate a 6 second battery charge.
Once the UPS is turned on via the ON / OFF button if the battery voltage drops below 18VDC the battery will be
considered abnormal.
3.2 DIN24240DC / DIN24480DC Input
NOTE
As long as live 24V DC is supplied to the UPS input terminals, the DC output terminals
will be live in Bypass and Line operation modes.
8.1 Troubleshooting
Wiring.
4.2 Extended Battery Module Wiring
.
Eaton Din Rail UPS Advanced User Guide 934139—Rev A
.
13

Publicidad

loading

Este manual también es adecuado para:

Din24480dcBpdin24xl