C C h h a a p p t t e e r r 9 9 S S p p e e c c i i f f i i c c a a t t i i o o n n s s
9 9 . . 1 1
S S p p e e c c i i f f i i c c a a t t i i o o n n s s
Table 3. DC Input Characteristics
Input Rated Voltage
Input Rated Voltage
Input Voltage Range
Efficiency
Table 4. DC Output Characteristics
DC Output Current
Line mode & Battery mode DC output
voltage
Turn on time
Transfer time
Table 5. Protection Characteristics
Input Over-Voltage Protection
Input Under-Voltage
Over Current Protection
Short Circuit Protection
Over Temperature Protection
Table 6. Battery Characteristics
Battery Type
Charging Current
Recharge time
DIN24240DC
22.6V±0.5V turn on to LM
21.6V±0.5V turn off to BM
28.6V±0.5V turn off to BM
27.6V±0.5V turn on to LM
Line mode:≥ 95%
Battery mode: ≥ 95%
DIN24240DC
0A~10A
Vin – Vout ≤ 0.6Vdc
DIN24240DC
The output should to protect by auto-recovery mode.
*Latch after 3 consecutive times if fault condition is not removed
The output should to protect by auto-recovery mode
*Latch after 3 consecutive times if fault condition is not removed(with battery
The output should to protect by auto-recovery mode
DIN24240DC
12V/4.5AH * 2 lead acid battery in series
Eaton Din Rail UPS Advanced User Guide 934139—Rev A
DIN24480DC
24VDC
21.6~28.6VDC
Line mode:≥ 95%
Battery mode: ≥ 95%
DIN24480DC
0A~20A
< 1s
<10 ms
DIN24480DC
< 30v
> 20v
condition)
DIN24480DC
< 0.75A
< 8 hours
21