Descargar Imprimir esta página

Eaton DIN24240DC Manual De Instrucciones página 14

Ocultar thumbs Ver también para DIN24240DC:

Publicidad

Idiomas disponibles

Idiomas disponibles

1.
Locate the DC Input / Output terminal blocks on the top or front panel of the EBM.
2.
Ensure that the proper wire gauge is being used per
3.
Strip the wire insulation back about 0.35 inches (9mm) of all positive and negative wires being used for DC
Input/Output/Battery connections.
4.
Insert the red wire into the EBM (+) terminal closest to the DIN Rail UPS or previous EBM( if multiple
EBMs are being used ).
5.
Insert the black negative wire to the negative (-) terminal of the EBM closest to the DIN Rail DC UPS.
Tighten the screws to the specified torque rating in .
For maximum contact and safety, please ensure that the DC cables wire strands are fully inserted inside the
DC terminals.
6.
With a voltmeter, verify that 24VDC is present across all positive and negative terminals.
7.
Power the UPS ON, see
Figure 6. EBM Wiring
Input
Output
Table 2. Recommended EBM Wire Size
Connection
Battery Terminals
IMPORTANT
5.1 Startup and Normal Operation
External Battery #1
External Battery #2
Wire Size (AWG)
12 AWG (4 sq. mm)
Eaton Din Rail UPS Advanced User Guide 934139—Rev A
Extended Battery Module Wiring
Table 2
.
.
Torque N-m (in-lb)
0.6 (5.3 in-lb)
11

Publicidad

loading

Este manual también es adecuado para:

Din24480dcBpdin24xl