OPERATING INSTRUCTIONS
en
6.3
Setting
24
O P E R A T I N G I N S T R U C T I O N S | WTF9-3
% of sensing distance
5
0
–5
1
2
6%/90%
18 %/90%
–10
–15
–20
0
100
200
300
400
(3.94)
(7.87)
(11.81)
(15.75)
Figure 6: Characteristic curve
Black object, 6% remission factor
1
Gray object, 18% remission factor
2
White object, 90% remission factor
3
1
20
250
2
20
3
20
100
200
300
0
(3.94)
(7.87)
(11.81)
Sensing range
1
Sensing range on black, 6 % remission
2
Sensing range on grey, 18 % remission
3
Sensing range on white, 90 % Remission
Figure 7: Bar graph
Sensing range adjustment
The sensing range is adjusted relative to the background with the potentiometer.
Clockwise rotation: Sensing range increased; counterclockwise rotation: Sensing range
reduced. Turn the potentiometer clockwise until the yellow LED lights up. Afterwards,
only turn the potentiometer counterclockwise as far as is needed so that the yellow LED
no longer lights up. When an object is moved into the path of the beam, the yellow LED
must light up. If the yellow LED does not light up during object detection, repeat the
adjustment process, or reduce the distance between the sensor and background and
then repeat the adjustment process.
Please refer to the enclosed "IO-Link photoelectric sensors" operating instructions for
information about adjusting the IO-Link sensing range.
The sensor is adjusted and ready for operation.
3
90%/90%
500
600
700
(19.69)
(23.62)
(27.56)
Distance in mm (inch)
380
600
400
500
600
(15.75)
(19.69)
(23.62)
Distance in mm (inch)
8028048/2022-09-05 | SICK
Subject to change without notice