SECTION 8: MAINTENANCE
WARNING: DO NOT ALLOW REACTOR
QUARTZ SLEEVE ADAPTER NUT TO LOOSEN.
3. Unthread the Water Tight Connector Fitting from the
White Quartz Sleeve Adapter Nut.
4. Carefully slide the lamp cable's adapter fitting and
lamp out of the quartz sleeve (through the White
Quartz Sleeve Retaining Nut). With part of the UV
lamp outside of the vessel, disconnect the lamp
cable's 4-Pin Connector from the UV lamp. Use
caution connecting/ disconnecting UV lamps in
vessels mounted vertically. To prevent breakage,
be careful not to drop the UV lamps into the quartz
sleeve(s). UV Lamps may be hot, handle with care.
5. With the lamp disconnected from the 4-Pin
Connector, carefully slide the lamp out of the quartz
sleeve and place in a safe location to avoid breakage
UV Lamp Recycling
Disposal of fluorescent bulbs and other mercury-
containing bulbs are regulated under the Resource
Conservation and Recovery Act, the Universal Waste
Rule and Subtitle C of the hazardous waste regulations.
Refer to https://www.epa.gov/hw/universal-waste to
learn more about proper lamp disposal.
Lamp Installation
See Page 14 for UV Lamp installation procedure.
Quartz Sleeve Removal
Purpose
To inspect or replace broken quartz sleeve(s) in order to
maintain required/expected UV intensity.
Frequency
Quartz Sleeve(s) should be removed, inspected and
cleaned at least once annually (water quality conditions
may warrant more frequent inspections/cleaning).
Fouled quartz sleeves absorb UV light and therefore
may reduce the UV intensity.
Parts and Equipment Required
• Quartz Sleeve(s)
• Quartz Sleeve Retaining Nut with O-Ring
• Adjustable Wrench
• Clean Cotton or Silicon Gloves
• Personal Protective Equipment
• White Retaining Nut Tightening Tool (provided with
the UV system)
General risk due to pressurized piping and UV
vessel!
General risk due to electricity!
Quartz Sleeves are fragile and potentially
dangerous if broken. Handle with care.
WARNING:
SERVICING WHILE
PRESSURIZED CAN CAUSE
SEVERE INJURY.
LOCK OUT SOURCE AND RELIEVE
PRESSURE BEFORE SERVICING.
BioShield® PRO UV System Installation and User's Guide
19