follow standard IEC/HD 60364-7-702 and required national rules for swimming
pools. Consult your local dealer for more information.
• The appliance may not be installed close to combustible materials, or the air duct
inlet of an adjacent building.
• During installation, troubleshooting and maintenance, pipes may not be used as
steps: the pipe could break under the weight, spilling coolant and possibly causing
serious burns.
• When servicing the appliance, the composition and state of the heat transfer fluid
must be checked, as well as the absence of any traces of coolant.
• During the appliance's annual sealing test in accordance with applicable legislation,
the high and low pressure switches must be checked to ensure that they are
securely fastened to the cooling circuit and that they cut off the electrical circuit
when tripped.
• During maintenance work, ensure there are no traces of corrosion or oil around
the cooling components.
• Before beginning work on the cooling circuit, stop the appliance and wait for a few
minutes before fitting the temperature and pressure sensors. Some elements such
as the compressor and piping may reach temperatures in excess of 100°C and high
pressures with the consequent risk of severe burns.
TROUBLESHOOTING
• All brazing must be carried out by qualified brazers.
• Replacement pipes must always be made of copper in compliance with standard
NF EN 12735-1.
• Leak detection; pressure test:
- never use oxygen or dry air (risk of fire or explosion)
- use dry nitrogen or the mixture of nitrogen and refrigerant indicated on the
information plate,
- the test pressure for both the high and low pressure circuits must not exceed 42
bar in cases where pressure gauges are connected to the appliance.
• The high pressure circuit pipes are made of copper and have a diameter equal to or
greater than 1''5/8. A certificate as indicated in §2.1 in compliance with standard
NF EN 10204 must be requested from the supplier and filed in the installation's
technical file.
• Technical data relative to the safety requirements of the various applicable directives
are indicated on the information plate. All this information must be recorded in the
appliance's installation manual, which must be kept in its technical file: model,
code, serial number, maximum and minimum OT, OP, year of manufacture, CE
marking, manufacturer's address, coolant and weight, electrical parameters,
thermo-dynamic and acoustic performance.
LABELLING
• Equipment shall be labelled stating that it has been decommissioned and emptied
of refrigerant.
• The label shall be dated and signed.
• For appliances containing flammable refrigerants, ensure that there are labels on
the equipment stating the equipment contains flammable refrigerant.
RECOVERING
• When removing refrigerant from a system. either for servicing or decommissioning,
it is recommended good practice that all refrigerants are removed safely.
• When transferring refrigerant into cylinders, ensure that only appropriate
refrigerant recovery cylinders are employed. Ensure that the correct number of
cylinders for holding the total system charge is available. All cylinders to be used
are designated for the recovered refrigerant and labelled for that refrigerant (i.e.
special cylinders for the recovery of refrigerant). Cylinders shall be complete with
pressure-relief valve and associated shut-off valves in good working order. Empty
recovery cylinders are evacuated and. if possible. cooled before recovery occurs.
• The recovery equipment shall be in good working order with a set of instructions
EN
3