WIKA T53.10 Manual De Instrucciones página 8

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

2. Safety
2.3.1 Conditions for Model T53.10.0NI from type examination
certificate KEMA 06ATEX149 X
Zone 2 approval
GB
Entity parameters:
U
i
L
i
C
i
T1 ... T4
T5
T6
Sensor (terminal 3, 4, 5 and 6):
Uo : 5.7 VDC
Io : 8.4 mA
Po : 12 mW
Lo : 200 mH
Co : 40 µF
Specific conditions for safe use
For use in potentially explosive atmosphere of flammable gasses,
vapours or mists, the transmitter T53.10.0NI shall be mounted in an
enclosure providing a degree of protection of at least IP 54 in accord-
ance with EN 60 529.
For use in the presence of combustible dusts, the transmitter shall be
mounted in an enclosure providing a degree of protection of at least
IP 6X in accordance with EN 60 529. The surface temperature of the
enclosure shall be determined after installation of the transmitter.
8
T53.10.0NI
Zone 2 Ex nL IIC/
Ex ic IIC
32 VDC
1 µH
2.0 nF
T
≤ 85 °C
a
T
≤ 75 °C
a
T
≤ 60 °C
a
WIKA Operating Instructions Temperature Transmitter T53
II 3 GD Ex nA [nL] IIC T4 ... T6
II 3 GD Ex nL IIC T4 ... T6
II 3 GD Ex nA [ic] IIC T4 ... T6
II 3 GD Ex ic IIC T4 ... T6
Zone 2 nA
32 VDC
T
≤ 85 °C
a
T
≤ 75 °C
a
T
≤ 60 °C
a
FNICO (FISCO)
17.5 VDC
1 µH
2.0 nF
T
≤ 85 °C
a
T
≤ 75 °C
a
T
≤ 60 °C
a

Publicidad

Tabla de contenido
loading

Tabla de contenido