Indoor Unit Installation
Installation Instructions – Indoor unit
PRIOR TO INSTALLATION: Before installing the indoor unit, refer to the label on
the product box to make sure that the model number of the indoor unit
matches the model number of the outdoor unit.
Step 1: Select installation location
Before installing the indoor unit, you
must choose an appropriate location.
The following are standards that will
help you choose an appropriate
location for the unit.
Proper installation locations meet
the following standards:
Good air circulation
Convenient drainage
Noise from the unit will not disturb
other people
Firm and solid—the location will not
vibrate
Strong enough to support the weight
of the unit
A location at least one meter from all
other electrical devices (e.g., TV, radio,
computer)
DO NOT
install unit in the following
locations:
Near any source of heat, steam, or
combustible gas
Near flammable items such as
curtains or clothing
Near any obstacle that might block
air circulation
Near the doorway
In a location subject to direct
sunlight
NOTE ABOUT WALL HOLE:
If there is no fixed refrigerant piping:
While choosing a location, be aware
that you should leave ample room for
a wall hole (see Drill wall hole for
connective piping step) for the signal
cable and refrigerant piping that
connect the indoor and outdoor units.
The default position for all piping is
the right side of the indoor unit (while
facing the unit). However, the unit can
accommodate piping to both the left
and right.
Refer to the following diagram to
ensure proper distance from walls and
ceiling:
200cm (78.7in)
or more
50cm (19.7in)
or more
V.3
30cm (11.8in) or more
5cm (2in)
or more
50cm (19.7in)
or more
20