Descargar Imprimir esta página

Hitachi PC-ARH1E Manual De Instalación Y Funcionamiento página 10

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 35
ELECTRICAL WIRING
3 ELECTRICAL WIRING
3.1 STANDARD WIRING
!
C A U T I O N
Attach the ring core (black) (accessory) when installing the unit.
Insert the controller cable into the ring core, 2 turns, as shown in the
left figure, before connecting to the terminal board. If wiring is 0.75
mm
it is necessary to peel the outside cover.
2
Fix the cable by using the band (accessory)
3.2 ELECTRICAL WIRING FOR MULTIPLE UNITS
This remote control switch can control sixteen units, as the maximum.
!
C A U T I O N
Use 0.3-0.75 mm
cable (maximum total cable length 30m). If the total cable length is longer than 30m, use twist pair cable (1P–0.75 mm
2
(maximum total cable length 200m). When use with the control timer, (max. total cable length 100m). Using other cables may cause malfunction
due to noise.
Keep a distance of more than 30 cm between the remote control / indoor unit transmission cables and the power wiring.
If installed within 30 cm, put the cables in a conduit tube and earth (type-D; ≤ 100Ω) one end of the pipe. Without this procedure, malfunction or
failure of the air conditioner due to noise may occur.
When multiple indoor units are simultaneously controlled, set addresses for refrigerant cycle and indoor units. Especially when the indoor units from
multiple refrigerant cycle are simultaneously controlled, transmission abnormality may occur due to address duplication.
For more information about wiring remote control switch-indoor unit and setting indoor units addresses, see the indoor units "INSTALLATION
MANUAL".
Do not leave any space at the cable opening of the remote controller case. If there is any space, cover it with, e.g., vinyl tape to avoid trouble caused
by dew or insects entering into the controller case.
To use two remote controller (main/sub controllers), follow the procedure in "7 OPTIONAL FUNCTION" to configure main/sub remote controllers.
Before setting, turn OFF the power of all the indoor units connected to the remote control switch.
2
PMML0497 rev.1 - 12/2020
Maximum 16 indoor units
Terminal Board
M3.5
screws
Twist Pair cable:
1 P - bigger than 0.75mm
Terminal Board
M3.5
screw
2
Band
Ring Core
Control
wiring
)
2

Publicidad

loading