OPTIONAL FUNCTION
No.
Item
Optional function
Control in "Automatic" indoor
fan speed mode (supporting
High H)
Models:
RCI-FSN4
RCIM-FSN4E
51
EF
RCD-FSN3
RPC-FSN3
RPI-FSN5E
RPI-FSN3E(P)E(-f)
RPIM-FSN4E(-DU)
RPk-FSN(H)3M
52
Not available
F0
Automatic OFF timer setting
Models:
RCI-FSN4
RPC-FSN3
RPk-FSN3M
RPI-FSN5E
RPIM-FSN4E(-DU)
RCD-FSN3
53
F1
RCIM-FSN4E
RPI-FSN3(P)E
Automatic OFF timer setting
Models:
RPF(I)-FSN2E
Remote control main-sub
54
F2
setting
Automatic reset of setting
55
F3
temperature
56
Automatic reset time
F4
15
PMML0497 rev.1 - 12/2020
Individual
Settings
Setting
00
Function disabled
01
Function enabled
"- -"
-
permanent
Function disabled
00
(Factory setting)
01
1 hour
02
2 hours
03
3 hours
04-24
(04-24) hours
×
0A
30 minutes
0B
90 minutes
0C
40 minutes
0D
45 minutes
0E
50 minutes
0F
55 minutes
Function disabled
00
(Factory setting)
01
1 hour
02
2 hours
×
03
3 hours
04-24
(04-24) hours
0A
30 minutes
0B
90 minutes
Main (Master remote control)
00
(Factory setting)
×
01
Sub (Slave remote control)
Function disabled
00
(Factory setting)
×
01
Function enabled
00
30 minutes (factory setting)
01
15 minutes
×
02
60 minutes
03
90 minutes
Setting conditions
This function limits the speed
of the indoor fan when room
temperature is close to the setting
temperature, allowing to reach
High H speed.
This function sets an automatic
OFF timer to switch OFF the
indoor units controlled by the
remote control switch (when the
units have been started by remote
control).
}
(Do not set the values "0C"-"0F"
when two remote control switches
are used in the same remote
Do not set these
control group)
when two wired
controllers are
used.
This function is used to set the
automatic timer to switch off
when the unit has been started by
remote control.
This function is used to define
which remote control switch is
used as master or slave, when two
remote controllers are connected
to one indoor unit.
This function is used to limit unit
operation and save energy.
The setting temperature is
automatically set to the value
defined with functions "F5" or "F6",
according to the current operation
mode, after the time set with
function "F4" has passed since
the last manual change of setting
temperature.
In case that the values of "F5" or
"F6" are out of the limits set with
functions "FC" and "Fd", limitations
set by "FC" and "Fd" have priority.
This function sets the automatic
reset time delay for function F3.
Description