Basic Operation
(continued)
Front Panel Indicator Lights
continued
"BYPASS" LED: This yellow light will flash to indicate that the UPS's
DC/AC inverter is deactivated and the UPS is in the "Bypass" mode.
During normal operation this LED will light briefly when the unit is
plugged in, but if an internal fault or overload occurs this light will flash
constantly and the fault LED will illuminate to show that connected
equipment will receive filtered AC mains power, but will not receive
battery power during a blackout. In this case, contact Tripp Lite for
service. If the UPS has been placed into Economy Mode (available on
select UPS systems), it configures an online UPS to function as a
switching UPS. When the UPS system is in Economy Mode, it operates
at increased efficiency while AC utility power is available (within +/-
10% nominal) and switches to battery power if AC utility power is
interrupted. The yellow "BYPASS" LED will remain on when the UPS
system is in Economy Mode. (For more information on how to access the
Economy Mode, please refer to the PowerAlert software User's Manual.)
"FAULT" LED (select models only): This red light will flash when
your UPS detects an internal fault (overheating, overvoltages, etc.). If
the light persists after restarting the UPS, contact Tripp Lite for
service.
"LOAD ACTIVE METER" LED: This green light will illuminate
when your UPS is receiving AC power to indicate that the set of four
dual-function LEDs is displaying the load level of your UPS.
"BATT ACTIVE METER" LED: This green light will illuminate
when your UPS is operating from battery power to indicate that the set
of four dual-function LEDs is displaying the battery charge level of
your UPS. Note: the "ON BATT" LED will also be illuminated.
"OVERLOAD" LED: This red light will illuminate constantly to indicate
that your UPS's capacity has been exceeded while it is in on-line operation.
The UPS alarm will beep continuously. Immediately remove overload
until light and alarm go off. If you do not immediately remove the
overload, the UPS will transfer from on-line to bypass operation.
"BATT LOW" LED: This yellow light will illuminate when your UPS's
battery charge level is low. The UPS alarm will beep until either the
battery charge is depleted or the batteries are adequately recharged.
"ON BATT" LED: This green light will illuminate constantly to
indicate that AC line voltage is not present and your UPS is providing
your equipment with battery power. The UPS will also beep every two
seconds, unless silenced by the "ON/TEST" Button. When this light is
illuminated, you can monitor the battery charge level of your UPS on
the "BATT ACTIVE METER" LEDs.