Adding refrigerant
After finishing vacuuming, exchange the vacuum pump with a refrigerant canister and start additional charging of
refrigerant.
Calculation of additional refrigerant charge amount
Refrigerant charge amount at shipment from the factory does not include the refrigerant for pipes at the local site.
For refrigerant to be charged in pipes at the local site, calculate the amount and charge it additionally.
NOTE
If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without
additional refrigerant.
Standard
MUP***1HT6P-UL
MMY-
072
MUP***1HT9P-UL
Amount of refrigerant
lbs
charged in factory
kg
High heat
MUP***H1HT6P-UL
MMY-
072
MUP***H1HT9P-UL
lbs
Amount of refrigerant
charged in factory
kg
Additional amount of refrigerant charge at site = [1] + [2] + [3] + [4]
[1] Compensation amount of refrigerant based on outdoor unit capacity type. (Table 1)
[2] Additional amount of refrigerant charge based on liquid pipe size.
Real length of liquid pipe × Additional amount of refrigerant charge per liquid pipe 39.4" (1 m). (Table 2)
[3] Additional amount of refrigerant charge based on liquid pipe size. (Table 3)
[4] Corrected amount of refrigerant based on outdoor unit diversity. (Table 4)
Table 1-1
Standard
Combination outdoor units
Outdoor unit
capacity type
Unit 1
Unit 2
072
072
-
096
096
-
120
120
-
144
144
-
168
168
-
192
096
096
216
144
072
240
144
096
264
168
096
288
144
144
312
168
144
336
168
168
360
168
096
384
144
144
408
168
144
432
168
168
456
168
168
480
168
168
31-EN
096
120
144
168
13.2
19.8
6.0
9.0
096
120
19.8
9.0
Compensation by outdoor unit capacity type
Unit 3
lbs
-
2.20
1.00
-
2.64
1.20
-
-1.10
-0.50
-
0.33
0.15
-
6.16
2.80
-
5.28
2.40
-
2.53
1.15
-
2.97
1.35
-
8.80
4.00
-
0.66
0.30
-
6.49
2.95
-
12.32
5.60
096
11.44
5.20
096
3.30
1.50
096
9.13
4.15
096
14.96
6.80
120
11.22
5.10
144
12.65
5.75
Table 1-2
High heat
Outdoor unit
capacity type
072
096
120
144
192
240
288
360
192
Table 2
Liquid pipe diameter
Additional amount of
refrigerant
Table 3 Additional amount of refrigerant for indoor unit
Table 3-1 Additional amount of refrigerant based on indoor unit capacity type
Indoor unit capacity type
Indoor unit capacity code
lbs
Additional amount of
refrigerant (kg)
※ If the outside air unit type (MMD-UP***1HFPUL) is connected, The additional amount refrigerant for outside air unit type
is 0 kg
Table 3-2 Additional amount of refrigerant for 4-way Cassette type (MMU-UP***1HP-UL)
Indoor unit capacity type
kg
Indoor unit capacity code
lbs
Additional amount of
refrigerant (kg)
kg
Table 3-3 Additional amount of refrigerant for Concealed Duct Standard Type (MMD-UP***1BHP-UL)
Indoor unit capacity type
Indoor unit capacity code
lbs
Additional amount of
refrigerant (kg)
kg
– 16 –
Combination outdoor units
Compensation by outdoor unit capacity type
Unit 1
Unit 2
Unit 3
lbs
072
-
-
-2.20
096
-
-
-1.65
120
-
-
3.30
072
072
-
-4.40
096
096
-
-3.30
120
120
-
6.60
096
096
096
-4.95
120
120
120
9.90
mm
6.4
9.5
12.7
15.9
19.1
22.2
[in]
[1/4"]
[3/8"]
[1/2"]
[5/8"]
[3/4"]
[7/8"]
lbs/ft
0.017
0.037
0.071
0.108
0.168
0.235
kg/m
0.025
0.055
0.105
0.160
0.250
0.350
007
009
012
015
018
021
024
027
030
7.5
9.5
12
15.4
18
21
24
27
30
0.44
0.88
kg
0.2
0.4
007
009
012
015
018
024
027
7.5
9.5
12
15.4
18
24
27
0.44
0.88
0.2
0.4
007
009
012
015
018
021
024
7.5
9.5
12
15.4
18
21
24
0.88
0.4
kg
-1.00
-0.75
1.50
-2.00
-1.50
3.00
-2.25
4.50
036
042
048
054
072
096
36
42
48
54
72
96
1.32
2.20
0.6
1.0
030
036
042
048
054
30
36
42
48
54
1.32
0.6
030
036
042
048
054
30
36
42
48
54
1.32
0.6
EN
EN
ID
32-EN