61-EN
5
Push [ 
 ] to black highlight the code (DN),
and then push [ 
 ] and [ 
 ] to set the
code number to [✱✱✱✱].
6
Push [ 
 ] to black highlight the data, and
then push [ 
 ] and [ 
 ] to set the data to
[✱✱✱✱].
7
After finishing setting the data of the code
(DN) number, push [ 
Set/Fix]
"Continue?" is displayed.
8
To set the data of other codes (DN) number,
push [ 
Set/Fix]
To not do other settings, push [ 
Return]
The changes are fixed, and the "Field setting
menu" screen returns.
"    " appears while data is changing.
To change settings of another outdoor unit,
repeat from Procedure 1.
– 31 –
12
Test run
Before test run
Confirm that the valve of the refrigerate pipe of the
outdoor unit is OPEN.
Before turning on the power, confirm that the
resistance between the terminal block of power
supply and the ground is more than 2 M using a
500 V megohmmeter.
Do not run the unit if it is less than 2 M .
CAUTION
Turn on the power and turn on the case heater of
the compressor.
To save the compressor when it is activated, leave
the power on for more than 12 hours.
Methods of test run
When executing a test run using
a remote control
Operate the system normally to check the running
condition using the wired remote control. Follow
the instructions in the supplied Owner's Manual when
operating the unit.
If you use a wireless remote control for operations,
follow the instructions in the Installation Manual
supplied with the indoor unit.
To execute a test run forcibly under the condition that
the thermostat automatically turns the unit off due to
the indoor temperature, follow the procedure below.
The forcible test run will automatically stop after
60 minutes to prevent continuous forcible running and
return to normal running.
CAUTION
Do not use forcible running except for a test run as it
overloads the unit.
Wired remote control
Be sure to stop the air conditioner before making
settings.
(Change the setup while the air conditioner is not
working.)
1
Push [ 
Menu] to open the "Menu"
2
Push and hold [ 
Menu] and [ 
 ] at the
same time to open "Field setting menu"
Push and hold 4 seconds.
3
In the "Field setting menu" screen, push
[ 
 ] and [ 
 ] to select "Test mode", and
then push [ 
Set/Fix]
Test mode is set, and returns to the "Field
setting menu" screen. Push the [ 
Return]
button 2 times, to open screen (2).
62-EN