Descargar Imprimir esta página

Daikin LMSEY1A09AVM01 Manual De Funcionamiento página 18

Ocultar thumbs Ver también para LMSEY1A09AVM01:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 81
8 Troubleshooting
Malfunction
Compressor stops. The
▪ Check if air inlet or outlet of the unit
unit is equipped with an
condenser
overtemperature device
obstacles. Remove any obstacles
which stops the
and make sure the air can flow freely.
compressor every time the
▪ Check
max. allowable
Correct if necessary.
temperature of motor
▪ Check operation of the condenser
windings is exceeded.
fan. If it is not working, contact your
Possible causes are:
dealer.
▪ Insufficient ventilation of
the room where the unit
is installed.
▪ Anomaly
in
mains
voltage.
▪ Faulty
operation
of
condenser fan.
Device reset is automatic
after temperature dropped
to normal.
The system stops
▪ Check if air inlet or outlet of outdoor
immediately after starting
or indoor unit is not blocked by
operation.
obstacles. Remove any obstacles
and make sure the air can flow freely.
The system operates but
▪ Check if air inlet or outlet of the unit
cooling is insufficient.
evaporator
obstacles. Remove any obstacles
and make sure the air can flow freely.
▪ Check if the evaporator inside the
cold room is not frosted up. Defrost
the unit manually, or shorten the
defrost operation cycle.
▪ Check if there are not too many
articles inside the cold room, see
Loading the goods. Remove a couple
of articles.
▪ Check
circulation inside the cold room.
Reorganise the articles inside the
cold room, see Loading the goods.
▪ Check if there is not too much dust on
the condenser. Remove the dust, see
To clean the interior.
▪ Check if there is cold air leaking out
of the cold room. Stop the air from
leaking outside.
▪ Check
temperature too high. Set the setpoint
appropriately, see To set the Set
Point.
▪ Check
temperature articles stored in the cold
room. Always store articles after they
have cooled down.
▪ Check if the door is not opened too
long. Reduce the opening time of the
door.
If after checking all above items, it is impossible to fix the problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).
Operation manual
18
Measure
is
not
blocked
by
power
supply
(voltage).
is
not
blocked
by
if
there
is
smooth
air
if
you
did
not
set
the
if
there
are
no
high-
8.1
Error codes: Overview
In case a malfunction code appears on the indoor unit user interface
display, contact your installer and inform the malfunction code, the
unit type, and serial number (you can find this information on the
nameplate of the unit).
For your reference, a list with malfunction codes is provided. You
can, depending on the level of the malfunction code, reset the code
by pushing the ON/OFF button. If not, ask your installer for advice.
The error codes are visible in the alarm menu.
To access the alarm menu and to reset an alarm or error code, see
"4.5 About the alarms" [ 4  13].
Display
Log
code
code*
Afr
29
Frost protection
AtS
30
Restart in pump down
CE
28
Configuration write error
cht
17
High condensing temperature warning
CHt
18
High condensing temperature alarm
COM
34
VCC communication error
dA
14
Delayed alarm from external contact
dor
15
Door open
E1
1
Probe 1 faulty or disconnected
E2
2
Probe 2 faulty or disconnected
E3
3
Probe 3 faulty or disconnected
E4
4
Probe 4 faulty or disconnected
E5
5
Probe 5 faulty or disconnected
E6
6
Probe S1H faulty or disconnected
E7
7
Probe S2H faulty or disconnected
Ed1
10
Defrost terminated after maximum time
Ed2
11
Defrost on second evaporator terminated
after maximum time
EHI
36
High power supply voltage alarm
ELO
37
Low power supply voltage alarm
Etc
9
Clock error
GHI
19
Generic alarm high threshold
GLO
20
Generic alarm low threshold
HA
21
Type HA HACCP alarm (high temp. during
operation)
HF
22
Type HF HACCP alarm (high temp. after
blackout)
HI
24
High temperature
IA
13
Immediate alarm from external contact
LO
23
Low temperature Ad
LP
32
Low pressure
Man
38
Output status overridden in manual mode
Pd
26
Maximum pump down time
rE
12
Control probe faulty or disconnected
rSF
31
Refrigerant leak alarm
SF
27
Configuration not completed correctly
SrC
35
Maintenance request
UCF
33
VCC operation error
* This is the code used to record and display the alarm in Daikin
User.
Description
LMSEY1A09/13 + LMSEY2A19/25
Daikin LMS
4P728169-1B – 2023.07

Publicidad

loading

Este manual también es adecuado para:

Lmsey1a13avm01Lmsey2a19aye01Lmsey2a25aye01