WEG CFW500-SFY2 Instrucciones Y Manual De Seguridad página 15

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation
STO1
STO2
(contact
(contact
between
between
XC7:2 and
XC7:4 and
XC7:3)
XC7:5)
Open
Open
Open
Closed
Closed
Open
Closed
Closed
Figure 2.3 on page 14
describes its operation.
STO1
STO2
GND
STO1
STO2
(voltage on
(voltage on
XC7:3)
XC7:5)
0 V
0 V
0 V
+ 24 V
+ 24 V
0 V
+ 24 V
+ 24 V
14 | CFW500
Table 2.3: Truth table for dry contacts operation
Safety Stop
Function
Frequency inverter remains in the safe state. Starting
Enabled
commands are not accepted in this state. HMI display
indicates alarm A0160
Frequency inverter trips to fault F0160 if such input
configuration lasts longer than 1 s. To reset this fault, STO1
Fault
and STO2 must be in the same logical state and the frequency
inverter must be de-energized and re-energized
Frequency inverter operates normally, accepting starting
Disabled
commands
illustrates the installation with OSSD, and
1
2
3
4
5
6
Figure 2.3: Installation using OSSD signals
Table 2.4: Truth table for OSSD signals
Safety Stop
Function
Frequency inverter remains in the safe state. Starting
Enabled
commands are not accepted in this state. HMI display indicates
alarm A0160
Frequency inverter trips to fault F0160 if such input configuration
lasts longer than 1 s. To reset this fault, STO1 and STO2 must
Fault
be in the same logical state and the frequency inverter must be
de-energized and re-energized
Frequency inverter operates normally, accepting starting
Disabled
commands
Frequency Inverter Behavior
Table 2.4 on page 14
Frequency Inverter Behavior

Publicidad

Tabla de contenido
loading

Tabla de contenido