Commissioning
NOTE!
The frequency inverter uses the 3
SS1-t safety function is requested. Therefore, when using SS1-t, only modify
this parameter during the configuration of the CFW500-SFY2.
P0108 - SS1-t Time
Adjustable
0 to 999 s
Range:
Properties:
sy
Access Groups
via HMI:
Description:
It defines the delay time of the SS1-t safety function to be programmed in the safety functions
module. If the delay time value is 0 seconds, the safety functions module is programmed with
the STO safety function.
NOTE!
P0108 is only visible on HMI and, therefore, can only be modified when the
safety functions module is in the programming mode.
P0109 - SS1-t Time Confirmation
Adjustable
0 to 999 s
Range:
Properties:
ro, sy
Access Groups
via HMI:
Description:
During the programming procedure of the safety functions module, it indicates the actual value
of the delay time programmed in the safety module for the user's confirmation.
NOTE!
P0109 is only visible on HMI and, therefore, can only be accessed when the
safety functions module is in the programming mode.
18 | CFW500
Ramp to decelerate the motor when the
rd
Factory
Setting:
Factory
Setting:
0 s