Safety Data - WEG CFW500-SFY2 Instrucciones Y Manual De Seguridad

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Safety
NOTE!
According to IEC/EN 61800-5-2, the deceleration ramp of the SS1-t safety
function may fail undetectably. Therefore, this function must not be used if this
failure could cause a dangerous situation in the final application.

1.3 SAFETY DATA

The safety data for the CFW500 frequency inverter equipped with the CFW500-SFY2 is
presented in
Table 1.1 on page
Safety functions
Safety category
PFD
avg
PFH (1/h)
MTTF
(y)
d
DC
avg
Proof test interval
Response/reaction time
OSSD test pulses
Safety input signals
Maximum discrepancy time between
safety input signals
Safety power supply
(*) This means that the lifetime, or mission time, of the product is limited to 20 years, i.e. the product shall be replaced after
20 years.
NOTE!
The control accessories of the CFW500 frequency inverter provide a + 24 Vdc
power supply (150 mA, PELV type), which can be used to supply the CFW500-SFY2.
NOTE!
General data about the CFW500 frequency inverter can be found in the user's
manual, available for download on the website: www.weg.net.
8 | CFW500
8.
Table 1.1: Safety data
Safe torque off (STO), as per IEC 61800-5-2
Stop category 0, as per IEC 60204-1
Safe stop 1 time controlled (SS1-t), as per IEC 61800-5-2
Stop category 1, as per IEC 60204-1
SIL 3, as per IEC 61508 / IEC 62061 / IEC 61800-5-2
PL e, category 4, as per EN ISO 13849-1
Interval between pulses on the same channel: > 8 ms
Interval between pulses on different channels: > 4 ms
SELV type according to IEC 60950-1
or PELV type according to IEC 60204-1
< 2.74 . 10
-4
< 3.13 . 10
-9
> 1600 years
> 93 %
20 years
(*)
< 100 ms
Pulse duration: < 1 ms
ON: 15 Vdc ... 30 Vdc
OFF: < 2 V
1 s
+ 24 Vdc ± 15 %,

Publicidad

Tabla de contenido
loading

Tabla de contenido