4) Set parameter P0108 to the desired delay time value, for example, 15 s, as shown below.
Then, press the "ENTER" key. At this point, the display backlight starts to flash and the user
must confirm the programmed value by means of parameter P0109.
5) To confirm the programmed value, access parameter P0109 and check if the displayed
value in P0109 is the same as that programmed in P0108. If the values are the same, press
the "ENTER" key to confirm. At this point, the display back should stop blinking. In case of
different values for P0108 and P0109, the user must press the "ESC" key, which aborts the
programming procedure and trips fault F0160.
NOTE!
If the programming procedure of the delay time fails or is aborted, the last
programmed value is kept.
NOTE!
If the programming procedure stays idle for more than 2 minutes, the frequency
inverter trips fault F0160. To reset this fault, de-energize and re-energize the
frequency inverter.
Commissioning
CFW500 | 21