OPERATION
System Diagnostics Faults
System Diagnostics Faults
Fault
Flashing LED
Cycle Fault
NONE
Hardware Fault RUN & FAULT
Locked Rotor
OFF
Max Start Time OFF & AUTO
No Current
HAND
Fault
Overload
HAND & OFF
Phase
HAND, OFF, &
Unbalance
AUTO
HAND & AUTO A stall condition occurs (0.5 sec @ 300% FLA and current slope not
Stall
Underload
AUTO
For technical assistance, parts, or repair, please contact:
800.701.7894 | franklinwater.com
10000012662 Rev. 000 11/22
Activates when the starter exceeds rate of 20 starts per minute.
The current drawn from the 24 V contactor terminals exceeds the rat-
ing of the contactor, the wrong size contactor is installed, or there is a
circuit board failure.
NOTE: Contactor terminals C+ & C- are for use with a Franklin Electric
contactor only. Do not connect to any other devices.
A locked rotor condition occurs for 0.5 seconds.
The motor takes more than 10 seconds to start.
No current is detected 10 seconds after a run command has been
received.
The load is greater than the trip current = 115% of FLA (1
A phase failure event occurs or any phase deviates by more than 25%
from the average when Smartstart
abled, the starter will trip if any phase deviates more than 80% of the
average.
decreasing). Disabled during startup
The current falls below the user-selected % threshold on the under-
load dial setting for 0.5 seconds and if the current is not increasing (0-
100% of overload setting).
Description
TM
is enabled. If Smartstart
Franklin Electric Co., Inc. | Oklahoma City, OK 73157-2010
Copyright © 2022, Franklin Electric, Co., Inc. All rights reserved.
2
t trip curve).
TM
is dis-