5.9.
SETTING THE PROTECTED PARAMETER "HEATING SETPOINT"
This parameter allows you to set the maximum temperature above which disable any resistance or accessory battery to water, which may be contained
in the plenum or accessories PLS PLSM (if the plenum or PLS PLSM not provide, this parameter will be considered);
To set the heating setpoint it is necessary to enter in the password protected menu (as shown in paragraph 11.7), using the navigation keys to run
through the operating parameters until the parameter
the navigation keys to select the desired value (the accepted range of values is from 12°C to 40°C, default value is 20°C). Then press the MODE/SELECT
key to confirm the selection and exit from the parameter modification mode.
Note: To enable the electrical resistance must set the AUX mode (see parameter 11.3). The water coil aftertreatment winter, if present, is auto-
matically activated in manual mode, AUX or AUTO, depending on the need.
Season parameter (SPH):
1
2
The appearance of the SET icon shows that the system is awaiting modifi-
cation of the parameter (default heating setpoint value 20°C)
3
Once the value is confirmed the name of the parameter is again dis-
played.
WARNING: Once in the password protected menu pressing the
navigation keys (
parameters. If during the display of the SEA parameter the (
key is pressed this exits the password menu and to return to the
password menu it is necessary to repeat the procedure detailed
in paragraph 11.7.
34
1811 - 4238020_01
SP
is displayed. Press the MODE/SELECT key to enter the parameter modification mode and use
H
,
) permits moving between the various
1
2
3
)
Activate parameter modifica-
tion mode
Set the desired heating setpoint
Confirm the selected value