5.12.
SETTING THE PROTECTED PARAMETER "BY-PASS"
The RePuro units provide cooling function through the intake of outside air untreated. The use of this function depends on the value selected in this
parameter, which can be:
• 0 = if this value is selected the freecooling function is disabled
• 1 = Bypass outdoor air with a period 20 minutes
• 2 = Bypass outdoor air with a period 40 minutes
To set the value of 0.1 or 2, you must enter the password-protected menu (as described in Section 11.7), using the navigation keys to run through
the operating parameters until the parameter BPF is displayed. Press the MODE/SELECT key to enter the parameter modification mode and use the
navigation keys to select the desired value (default value is 1). Then press the MODE/SELECT key to confirm the selection and exit from the parameter
modification mode.
Bypass outdoor air parameter (BPF):
1
2
The appearance of the SET icon shows that the system is awaiting modifi-
cation of the parameter (default value 1)
3
Once the value is confirmed the name of the parameter is again dis-
played.
WARNING: Once in the password protected menu pressing the
navigation keys (
parameters. If during the display of the SEA parameter the (
key is pressed this exits the password menu and to return to the
password menu it is necessary to repeat the procedure detailed
in paragraph 11.7.
,
) permits moving between the various
1
2
3
)
Activate parameter modifica-
tion mode
Select the desired value
Confirm the selected value
1811 - 4238020_01
37