7.1.
CS PARAMETER
This parameter allows enabling the writing of some registers (see tab...) through modbus controls by a supervisor or BMS.
The CS parameter values can be.
CS = 0 → Writing from modbus serial disabled
•
•
CS = 1 → Writing from modbus serial enabled
7.2.
TSA PARAMETER
This parameter allows you to select the type of probe used to read the outdoor air (SAE), see figure.
The TSA parameter values can be:
TSA = 0 → Outdoor air probe installed inside the recovery unit
•
TSA = 1 → Outdoor air probe installed outdoors
•
The probe that must be used for outdoor installation is the KSAE accessory.
1:
Possible modes of installation of the SAE probe
1
Probe position with TSA = 0
Position of the KSAE accessory probe
with TSA = 1