Applicable control settings
When connecting an optional P.C. board (sold separately) for outdoor units, it is necessary to change the settings
of the outdoor unit.
All are set to [Standard (factory setting)] at the time of shipment, so change the settings of the outdoor unit as
necessary.
The settings can be changed by operating the switches on the interface board.
In the TU2C-Link communication system, it can also be done by operating the wired remote control.
Applicable controls setup
(settings at the site)
Basic procedure
Be sure to stop the air conditioner before making settings.
(Change the setup while the air conditioner is not working.)
CAUTION
Set only the Code (DN) number shown in the following table: Do NOT set any other Code (DN) number.
If a Code (DN) number not listed is set, it may not be possible to operate the air conditioner or other trouble with
the product may result.
When switching settings from the interface P.C. board of the outdoor unit
1
Set the rotary switch of the interface P.C. board on the outdoor unit to SW01= [9], SW02= [1] and
SW03= [1].
2
The 7-segment display shows "d n.S E t".
3
When SW04 is pushed, the 7-segment display switches to "d n.0 0 1" and the outdoor unit Code (DN)
number [001] is displayed.
4
Change outdoor unit Code (DN) number [
Push SW05 to advance the code. Push and hold SW05 to advance in 5 steps.
Push SW06 to return the code. Push and hold SW05 to return in 5 steps.
5
When SW04 is pushed, the 7-segment display blinks "d.* * * *" and the setting data [
set is displayed.
6
Change setting data [
] with SW05 or SW06.
Push SW05 to advance the data. Push SW06 to return the setting data.
7
Push and hold SW04 for more than 2 seconds.
When the flashing stops and remain lit on the display, the setting is complete.
(To return to the item code setting after completing the setting, or to return to the item code setting
without setting, push SW04 once.)
8
Set the rotary switch on the interface P.C. board of the outdoor unit back to SW01= [1],
SW02= [1], SW03= [1].
9
Reset the power of the outdoor unit (power off for one minute or more).
59-EN
] with SW05 or SW06.
] being
Interface P.C. board of header unit
3,5,7
When switching from the wired remote control
(RBC-AWSU52-UL)
Basic procedure
Be sure to stop the air conditioner before making
settings.
(Change the setup while the air conditioner is not
working.)
Field setting menu (2/3)
6.Setting louver position
7.Setting timer operation mode
8.Easy I.DN setting
9.DN Setting
9.DN setting
10.Reset Power Consumption data
– 30 –
4,6
4,6
2,3,5,7
1,8
1
Push [ 
Menu] to open the "Menu"
2
Push and hold [ 
Menu] and [ 
 ] at the
same time to open "Field setting menu"
Push and hold 4 seconds.
3
In the "Field setting menu" screen, push
[ 
 ] and [ 
 ] to select "DN setting", and
then push [ 
Set/Fix]
4
Push [ 
 ] and [ 
 ] to select "Outdoor
unit", and the push [ 
Set/Fix]
The fan of the selected outdoor unit runs. The
outdoor unit can be confirmed for which to
change settings.
EN
EN
ID
60-EN