Powering up and Startup
Seq
Indication on the Display / Action
13
If necessary, modify the content of "P0407
– Motor rated power factor", or press the
key
During the Self-Adjustment the HMI will
15
simultaneously indicate the status of "RUN"
and "CONF". And the bar graph indicates
the progress of the operation.
And the bar graph indicates the progress
of the operation. The Self-Adjustment can
be interrupted at any time by means of the
key
17
The result of Self-Adjustment is the value in
ohms of the motor stator resistance shown
in P0409.
This is the last parameter of the Self-
Adjustment of the V V W control mode.
Press the key
parameter P0202.
19
Through the keys
desired menu or press the key BACK/ESC
again to return directly to the monitoring
mode of the HMI.
32 | CFW500
CALL NOW 800-985-6929
http://www.automatedpt.com
for the next parameter.
.
to return to initial
and
, select the
Figure 5.3: Sequence of the startup group for V V W control
http://www.automatedpt.com
Seq
Indication on the Display / Action
14
At this point, the HMI shows the option to
do the self-adjustment. Whenever possible,
perform the self-adjustment. Thus, to
activate the self-adjustment, change the
value of P0408 to "1".
At the end of the Self-Adjustment, the value
16
of P0408 automatically returns to "0", as
well as the Status of "RUN" and "CONF"
are cleared.
Press the key
18
To exit the STARTUP menu, just press
BACK/ESC.