CORRECT
ATTENTION!
Only the motor frame shall be grounded.

3.2.7 Control and Signal Connections

The control connections (digital inputs and relay outputs) are made through the terminals (refer
to figure 3.9).
Terminal
Description
A1
Electronics Supply
A2
Grounding
Terminal
Factory Default
DI1
Starts/Stops Motor
DI2
Fault reset
DI3
Fault reset
13
Relay 1 output - Operation
14/23
Relay common point
24
Relay 2 output - Full voltage
NOTE!
It is recommended to use shielded cables for the Dix inputs when using long cables
(above 30m) in noisy enviroments. The metallic shield and A2 must be grounded.
CORRECT
Table 3.9: Description of the control connector pins
Voltage: 110 to 240 Vac (-15 % to +10 %)
(models from 17 A to 200 A)
110 to 130 Vac or 208 to 240 Vac
(-15 % to 10 %) (models from 255 A to 412 A).
Only for the 255 to 412 A models
3 isolated digital inputs
Voltage: 110 to 240 Vac (-15 % to +10 %)
Current: 2 mA Max.
Contact capacity:
Voltage: 250 Vac
Current: 1 A
Figure 3.9: Control terminals of the Soft-Starter SSW-08
Installation and Connection
INCORRECT
INCORRECT
Specifications
Specifications
3
Torque Nm
(in lb)
0.5 (4.5)
SSW-08 | 19