Connection check-up
1. Check individual wire installation by tugging firmly.
2. Firmly tighten cable glands and insert blanking plugs in unused cable entries.
3. Remove o-ring from lid.
4. Reinstate lid and screw in until mechanical stop. Wind back lid by one turn.
5. Mount o-ring by pulling it over the lid and tighten lid cover until you feel friction from the o-ring on both sides. Wind lid by
one quarter of a turn to seal on the o-ring.
6. Reinstate and tighten lid lock screw where supplied.
7. Ensure that moisture does not penetrate to inside of electronics housing by creating a drip loop (bend cables downward)
immediately before cable glands.
Local user interface
Full graphical display
LED (for indication of key operation)
Capitance proximity keypad
Note
LUI timeout
If no key is pressed for 10 minutes, the display switches to show operation view.
Note
Operation does not require opening of the device. This means that the high degree of protection of IP67 and safety in
hazardous locations are guaranteed at all times.
10
SITRANS FCT030 transmitter