9 Troubleshooting
Code Behavior
of status dis-
play
F000
Lights up red
F001
Lights up red
F002
Lights up red
F003
Lights up red
F004
Lights up red
C101
Flashing red
S201
Flashing red
S202
Flashing red
S203
Flashing red
M301 Lights up blue
42
Diagnostics
Possible cause
Other errors
Not precisely speci-
fied
General software
A software error has
error
occurred.
Error during calibra-
An error within the
tion
device has occurred.
Error in the device
Error has occurred
settings
during the default
calibration.
The EEPROM is
faulty.
The configuration
data contain a
checksum error.
Teach-in procedure
An error has oc-
is faulty
curred during the
teach-in procedure.
Simulation active
The simulation is
currently being per-
formed.
Outside the admis-
The temperature
sible temperature
range is not admissi-
range
ble.
Switching output
An overload or short
overloaded
circuit has occurred
at the switching out-
put.
Outside the admis-
Voltage supply has
sible voltage supply
been exceeded.
range
Pollution degree
The coating thick-
detected
ness is inadmissible.
Remedy
Test the installation situation and
electrical connection. Return the
device if error is present.
chapter 11.3 "Returns",
Page 44
Restart the device.
Return the device.
chapter 11.3 "Returns",
Page 44
Restart the configuration.
Disconnect the voltage supply,
switch it on again and retrigger
the teach-in procedure. Return
the device if error is present.
chapter 11.3 "Returns",
Page 44
Exit the simulation.
Test the ambient temperature.
Insulate if necessary in the event
of excessively low temperatures,
cool if necessary in the event of
excessively high temperatures.
chapter 4 "Technical data",
Page 12
Test the electrical connection, in-
crease load resistance at the
switching output if necessary.
chapter 7 "Installation",
Page 28
Test the electrical connection for
correct installation.
chapter 6 "Electrical connec-
tion", Page 22
Clean the device.
chapter 10 "Maintenance and
cleaning", Page 43