6
Description of the pump
6.1
Anticipated noise levels
Installation and operating instructions • Wilo-Atmos BST • Ed.01/2023-07
Property
Electrical connection
1)
Note that water-glycol mixtures or fluids with a viscosity that is different to that of pure
water increase the power consumption of the pump.
The pumping data must be adjusted according to the higher viscosity of the fluid, regard-
less of the proportion of viscous substances.
Only use brand products with anti-corrosion inhibitors. Strictly follow the manufacturer's
instructions and safety data sheets!
When ordering spare parts, specify all data on the pump/motor rating plate.
Table 3: Technical data
•
Pump
•
Installation and operating instructions
Accessories must be ordered separately.
See catalogue for detailed list.
Monobloc pump, installation dimensions and hydraulics according to DIN EN 733. The
pumps can be installed directly in a sufficiently anchored pipe as an in-line pump or placed
on a base.
Pump with feet screwed to the pump housing.
For threaded pipe union pumps with screwed-on motor support.
Expected noise values as guideline.
Motor power P
Measuring surface sound-pressure level Lp, A [dB(A)]
2
[kW]
2900 rpm
0.55
73.1
0.75
74.4
1
75.6
1.1
76.0
1.5
77.3
1.85
78.2
2.2
78.9
3
80.2
4
81.4
5.5
82.8
7.5
84.1
9.2
84.9
11
85.7
15
87.0
18.5
87.9
22
88.6
30
89.9
37
90.8
1)
Spatial mean value of sound-pressure levels on a square measuring surface at a distance
of 1 m from the surface of the motor.
Table 4: Anticipated noise levels (50 Hz)
Value
1~220 V, 50 Hz (≤ 2.2 kW)
3~220 V, 50 Hz (≤ 3 kW)
3~380 V, 50 Hz (> 3 kW)
en
Note
Standard version
Standard version
Standard version
1)