11.2 Operating data
a)
measurement category according to IEC 61010-1 ................................... CAT III 600 V (II 1000 V)
b)
type of insulation ...................................................................................................... double, Class II
c)
housing type .......................................................................................................... double-composite
d)
degree of housing protection acc. to EN 60529 ...................................................................................... IP30
e)
pollution degree ................................................................................................................................ 2
f)
opening of measurement clamp ................................................................................... 30 mm (1.2")
g)
power supply of the meter .............................................................................. 3 x AAA 1.5 V battery
h)
diode test ................................................................................................. I = 1.0 mA, U
i)
continuity test ....................................................................................... acoustic signal for R < 50 Ω
................................................................................................................ measuring current <1.5 mA
j)
indication for range exceeding ......................................................................................... OL symbol
k)
low battery indication ................................................................................................... symbol
l)
measurement rate ............................................................................... 3 measurements per second
m)
INRUSH function
▪ sampling time................................................................................... 48 Hz (RMS), 400 kHz (clock)
▪ integration time .................................................................................................................... 100 ms
▪ sensitivity ............................................................................................................................ >2 A AC
n)
VFD function
▪ operating voltage .................................................................................................... 100...600 V AC
o)
range of the non-contact voltage detector .......................................... 100...1000 V AC (50/60 Hz)
p)
response time for PEAK function .......................................................................................... <10 ms
q)
temperature sensor ........................................................................................... type K thermocouple
r)
input impedance .................................................................................................... 10 MΩ (V AC/DC)
s)
AC read-out ........................................................................................... True RMS (A AC and V AC)
t)
AC bandwidth
▪ sine waveforms ........................................................................................................... 50...2000 Hz
▪ all waveforms .................................................................................................................. 50...60 Hz
u)
display............................................................................................................ 4 digit LCD with backlit
.................................................................................................. 4000 counts with function indicators
v)
dimensions ............................................................................................................ 220 x 80 x 39 mm
w)
meter weight
▪ CMP-402 ................................................................................................................................. 266 g
▪ CMP-402 (without batteries) .................................................................................................. 230 g
▪ CMP-403 ................................................................................................................................. 270 g
▪ CMP-403 (without batteries) .................................................................................................. 234 g
x)
operating temperature ........................................................................................................+5..+40C
y)
operating humidity ................... < 80% for temp. ≤ 31C decreasing linearly to 50% at temp. 40C
z)
storage temperature ......................................................................................................... -20..+60C
aa) storage humidity ....................................................................................................................... < 80%
bb) maximum operating altitude................................................................................................... 2000 m
cc)
Auto-Off function .................................................................................................................... 15 min
dd) compliance with the requirements of the following standards ................. EN 61326-1, EN 61326-2
......................................................................... IEC 61010-1, EN 61010-02-032, EN 61010-02-033
............................................ RoHS 2011/65/EU, (EU) 2015/863, EN 62479:2010, EN 50663:2017
ee) quality standard .................................................................................................................. ISO 9001
CMP-402 ● CMP-403 – USER MANUAL
< 3.0 V DC
0
65

Publicidad

loading

Este manual también es adecuado para:

Cmp-403Wmgbcmp402Wmgbcmp403