C C h h a a p p t t e e r r 4 4 O O p p e e r r a a t t i i o o n n s s
4 4 . . 1 1
U U P P S S S S t t a a r r t t - - U U P P w w i i t t h h S S U U P P D D M M B B P P 6 6 K K B B y y p p a a s s s s M M o o d d u u l l e e
Verify that the load equipment ratings do not exceed the UPS capacity to prevent an overload alarm.
1.
Check that the UPS is correctly connected to the bypass module (see
2.
Verify that the bypass module terminal block wiring is connected to the AC input and output source.
3.
Check that the Manual bypass switch is set to the BYPASS position.
4.
Set the upstream circuit breaker (not provided) to the "I" position (On) to switch On the utility power.
5.
Verify that the red BYPASS LED illuminates, indicating that the AC source now powers the load.
6.
Set the UPS input switch of the bypass module to the On position.
7.
Verify that the UPS is correctly powered and the UPS display panel illuminates (refer to the Smartonline
UPS User's Manual).
8.
Press and hold the UPS On button for three seconds to start the UPS.
9.
Put the UPS in internal Bypass mode (refer to the Smartonline UPS User's Manual).
10. Verify that the UPS is on Bypass mode by checking UPS display panel (refer to the Smartonline UPS User's
Manual).
11. Verify that the green UPS LED on the bypass module illuminates, indicating that UPS output power is
available on the bypass module.
Do not continue to the next step if the green UPS LED on the bypass module is Off or the load will be lost.
12. Set the Manual bypass switch to the UPS position: the BYPASS LED will turn Off indicating that the load is
now powered by the UPS.
13. Put the UPS in Normal mode (refer to the Smartonline UPS User's Manual).
NOTE
Do not connect any load equipment to the UPS outlets. Loads can only be connected to
the SUPDMBP6K outlets or hardwired output terminal blocks.
UPS
BYPASS
IMPORTANT
UPS
BYPASS
Eaton Tripp Lite Series SUPDMBP6K User Guide 934705—Rev A
3.3 Power Cable
Connection).
9