UPS Maintenance with SUPDMBP6K Bypass Module
11. Put the UPS in Normal mode (refer to the Smartonline UPS User's Manual).
12. Check that the UPS is in Online mode by checking UPS display panel (refer to the Smartonline UPS User's
Manual).
4 4 . . 3 3
U U P P S S M M a a i i n n t t e e n n a a n n c c e e w w i i t t h h S S U U P P D D M M B B P P 6 6 K K B B y y p p a a s s s s M M o o d d u u l l e e
To go to maintenance Bypass operation (follow the MANDATORY steps below):
1.
Put the UPS in internal Bypass mode (refer to the Smartonline UPS User's Manual),
2.
Verify that the UPS is on Bypass mode by checking UPS display panel (refer to the Smartonline UPS User's
Manual).
3.
Set the Manual bypass switch to BYPASS position. The red BYPASS LED will illuminate indicating that the
load is powered directly by the utility source.
4.
The UPS can now be safety serviced. If the UPS needs to be replaced see
4.2 UPS Replacement with SUPDMBP6K Bypass
Return to Normal Operation.
1.
Verify that the UPS is on Bypass mode by checking UPS display panel (refer to the Smartonline UPS User's
Manual).
2.
Verify that the green UPS LED light is illuminated, indicating that the UPS output power is available on the
bypass module.
Do not continue to next the step if the green UPS mode LED is Off or the load will be lost.
3.
Set the Manual bypass switch to the UPS position: the BYPASS LED turns Off indicating that the load is
now powered by the UPS.
4.
Put the UPS in Normal mode (refer to the Smartonline UPS User's Manual).
5.
Check that the UPS is in Online mode by checking UPS display panel ensuring the load is protected by the
UPS (refer to the Smartonline UPS User's Manual).
12
Eaton Tripp Lite Series SUPDMBP6K User Guide 934705—Rev A
UPS
BYPASS
Module.
IMPORTANT
UPS
BYPASS