Descargar Imprimir esta página

Eaton Tripp Lite Serie Manual De Instalacion Y Uso página 16

Ocultar thumbs Ver también para Tripp Lite Serie:

Publicidad

Idiomas disponibles

Idiomas disponibles

UPS Replacement with SUPDMBP6K Bypass Module
14. Check that the UPS is in Online mode by checking UPS display panel (refer to the Smartonline UPS User's
Manual) the load is now protected by the UPS.
4 4 . . 2 2
U U P P S S R R e e p p l l a a c c e e m m e e n n t t w w i i t t h h S S U U P P D D M M B B P P 6 6 K K B B y y p p a a s s s s M M o o d d u u l l e e
To disconnect the UPS from the bypass module follow the steps in this section.
1.
Put the UPS in internal Bypass mode (refer to the Smartonline UPS User's Manual).
2.
Verify that the UPS is on Bypass mode by checking UPS display panel (refer to the Smartonline UPS User's
Manual).
3.
Set the Manual bypass switch to "BYPASS" position. The red "BYPASS" LED will turn On indicating that
the load is supplied directly by AC source.
4.
Switch the UPS input switch to the Off position and wait 30 seconds.
5.
Wait for the UPS fans to stop and the display to turn off, the UPS can now be disconnected, as described
below:
Loosen the two screws that hold the I/O cord set in place on the bypass module, and then disconnect
the cable.
Remove the screws that hold the UPS I/O terminal block access cover in place.
10
Eaton Tripp Lite Series SUPDMBP6K User Guide 934705—Rev A
UPS
BYPASS
1
2

Publicidad

loading

Este manual también es adecuado para:

Tripp lite supdmbp6k