7. Operation
7.2

Operating modes

The Eaton 9PX front panel indicates the UPS status through the UPS indicators, see page 25.
Online mode
During Online mode, the
The UPS monitors and charges the batteries as needed and provides filtered power protection to your
equipment. Optional High Efficiency and Energy Saving settings minimize heat contribution to the rack
environment. See "User settings" on page 25.
Battery mode
When the UPS is operating during a power outage, the alarm beeps once every ten seconds and the
indicator illuminates solid. The necessary energy is provided by the battery.
When the utility power returns, the UPS transfers to Online mode operation while the battery
recharges.
If battery capacity becomes low while in Battery mode, the audible alarm beeps once every 3 seconds.
This warning is approximate, and the actual time to shutdown may vary significantly.
Shutdown all applications on the connected equipment because automatic UPS shutdown is imminent.
When utility power is restored after the UPS shuts down, the UPS automatically restarts.
Bypass mode
In the event of a UPS overload or internal failure, the UPS transfers your equipment to utility power.
Battery mode is not available and your equipment is not protected; however, the utility power
continues to be passively filtered by the UPS. The
Depending on overload conditions, the UPS remains in Bypass mode for at least 5 seconds and will
stay in this mode if three transfers to Bypass occur within 20 minutes.
The UPS transfers to Bypass mode when:
• the user activates Bypass mode through the front panel.
• the UPS detects an internal failure.
• the UPS has an overtemperature condition.
• the UPS has an overload condition listed on "Electrical output" on page 44.
The UPS shuts down after a specified delay for overload conditions listed on "Electrical output"
on page 44. The UPS remains on to alarm the fault.
High efficiency mode
In High Efficiency mode, the UPS operates normally on Bypass and transfers to Online (or Battery)
mode in less than 10 ms when utility fails. Transfers to High Efficiency mode will be active after 5
minutes of Bypass voltage monitoring: if Bypass quality is not in tolerance, then the UPS will remain in
Online mode.
Eaton recommends to use the HE mode only to protect I/T equipment.
To set the High Efficiency mode:
1. Put the UPS on Bypass: press any button to activate the menu options, select Control and Go to
Bypass.
2. Then press Escape and select Settings, In/Out settings, and High Efficiency mode.
3. Select Enabled and Enter to confirm.
4. The UPS transfers to High Efficiency mode in 5 minutes.
Standby mode
When the UPS is turned-off and remains connected to AC source, the UPS is in Standby mode.
Depending if Bypass Standby setting is enabled, the output is powered but not protected.
The battery recharges when necessary and the communication ports are powered.
Page 28
indicator illuminates solid and the UPS is powered from the utility.
indicator illuminates.
614-00205-01_EN