TABLE "D" - I/O CONFIG
DIP
1
Input IC1 configuration
2
3
4
Input SAFE1 configuration
5
6
Output AUX2 configuration
7
Lock configuration only with
8
I/O expansion board
(*) If "D" type devices are installed (as defined by EN12453), connect in unverified mode, foresee mandatory maintenance at least every six months.
32
- ZARA BT A80
INSTALLATION MANUAL
Logic
Default
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Description
DIP-1
DIP-2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
DIP-3
DIP-4
DIP-5
OFF
OFF
OFF
Input SAFE1 configured as PHOT TEST, verified photocell. *
Switches photocell testing on at start of operation. When
ON
OFF
OFF
beam is broken, photocells are active during both ope-
ning and closing. When beam is broken during closing,
movement is reversed only once the photocell is cleared.
Input SAFE1 configured as PHOT OP TEST, verified photo-
cell active only on opening. *
Switches photocell testing on at start of operation. In the
OFF
ON
OFF
event beam is broken, photocell operation is disabled
during closing. During opening, stops motion for as long
as the photocell beam stays broken.
Input SAFE1 configured as PHOT CL TEST, verified photo-
cell active only on closure.*
Switches photocell testing on at start of operation. In the
ON
ON
OFF
event beam is broken, photocell operation is disabled
during opening. During closing, movement is reversed
immediately.
Input SAFE1 configured as BAR, safety edge.*
Enables connection of devices not equipped with sup-
OFF
OFF
ON
plementary test contacts. The command reverses move-
ment for 2 sec.. If not used, leave jumper inserted.
Input SAFE1 configured as BAR OP TEST.*
Activates testing safety edges when starting operation.
ON
OFF
ON
The operation while opening causes the movement to be
reversed for 2 seconds, the operation while closing cau-
ses the automation to stop.
Input SAFE1 configured as BAR CL TEST.*
Activates testing safety edges when starting operation.
OFF
ON
ON
The operation while closing causes the movement to be
reversed for 2 seconds, the operation while opening cau-
ses the automation to stop.
Input SAFE1 configured as BAR 8K2, 8K2 SAFETY EDGE.*
ON
ON
ON
The command reverses movement for 2 sec.
DIP-6
DIP-7
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
DIP-8
ON
Input IC1 configured as START.
Operation according to 3-step logic.
Input IC1 configured as OPEN.
The command causes the leaves to open. If the input
stays closed, the leaves stay open until the contact is
opened. When the contact is open, the automated devi-
ce closes following the TCA time, where activated.
Input IC1 configured as CLOSE.
The command causes the leaves to close.
Input IC1 configured as PED.
The command causes the leaf to open to the pede-
strian (partial) opening position. Operation according to
3-step logic.
Input SAFE1 configured as PHOT, photocell non tested. *
Enables connection of devices not equipped with sup-
plementary test contacts. When beam is broken, photo-
cells are active during both opening and closing. When
beam is broken during closing, movement is reversed
only once the photocell is cleared. If not used, leave
jumper inserted.
Output AUX2 configured as SCA
With this configuration, the second radio channel auto-
matically becomes pedestrian.
Contact stays closed during opening and with leaf
open, intermittent during closing, open with leaf clo-
sed.
Output AUX2 configured as 2CH Radio.
The contact remains closed for 1s when the radio chan-
nel is activated.
Output AUX2 configured as courtesy light
With this configuration, the second radio channel auto-
matically becomes pedestrian.
The contact remains closed for 90 seconds.
Output AUX2 configured as area light.
With this configuration, the second radio channel auto-
matically becomes pedestrian.
Contact stays closed for the full duration of operation.
12V latch lock
EBP BT A 24V