4. Function
4.1. Visualization - LEDs status
The hybrid motor starter visualizes the operating modes with four LEDs. The functions of the LEDs are
oriented towards the NAMUR recommendation NE 44.
• The general device status is displayed by a green LED (PWR).
A blinking LED (PWR) indicates a message.
• The forward and reverse running of the drive is always displayed by means of a yellow LED (L or R).
• An internal or external error (process error: overcurrent, asymmetry) is indicated by a red LED (ERR).
After the control supply voltage is applied, all LEDs light up once as an LED test.
4.2. Diagnostics function
Thanks to the diagnostics functions, the hybrid motor starter is in a condition to identify several internal
errors as well as external errors (errors in the I/O).
• In case of a message, the power path remains switched on. Acknowledgment is not required.
• If an error is detected, the device is switched to a safe switch-off mode.
• All internal errors cannot be acknowledged and are saved in the device. The device then cannot be
operated.
• In the case of external errors, an error acknowledgment is required to exit the safe switch-off mode.
Explanation:
A = LED switched off / E = LED permanently lit / B = LED flashes approx. 2 Hz (50:50)
Status
Off
Operation readiness Supply voltage (control supply voltage) present
Drive switched on
Internal error
External error
in activation or I/O
(maintenance
requirement, NE44)
16
Description
No supply voltage (control supply voltage) present A
• Reverse running (L)
• Forward running (R)
Internal device error -
Device replacement required
Bimetal function:
The motor current is greater than the nominal
motor current specification (e.g. class 10 A):
Cooling time on! (20 minutes)
• Error in reverse running.
• Error in forward running.
"L" or "R" flashes after 2 minutes:
A manual reset is possible.
• Error in reverse running.
• Error in forward running.
Error when restoring the system state:
Checksum erroneous.
The thermal memory of the bimetal function is set
to the max. value.
The error must be manually acknowledged in
automatic mode.
LED: PWR ERR L R Error acknow-
Green Red Yellow
A
A A
E
A
A A
E
A
E A
E
A
A E
E
E
A A Not possible
E
B
E A Automatic
E
B
A E Automatic
E
B
B A
E
B
A B
E
B
B B
ledgement
-
-
1)
1)
Manual
Manual
Manual