5.4. Motor with brake
If a motor with a brake (connection in the mechanical motor brake) is connected, the 400 V AC brake must
be connected to the 2/T1 and 6/T3 connections. A 230 V AC-brake should be connected to the
4/T2 connection and the star point of the motor.
Please note: The motor current monitoring must be increased by the value of the brake (nominal
current brake). Set this as per the hybrid motor starter (see Item 4.3, page 18)!
5.5. Auxiliary relay connection
Auxiliary relay (e.g. PLC RSC 230UC/21, Order No.: 2966207) for activating the external brakes or
feedback to the PLC must be connected to the connections "4T2" and "N" of the system.
6. Technical data
Type
Input data
Rated control supply voltage U
as per IEC 60947-1 / UL 508/UL 60947-4-1A/UL 60947-1
Control supply voltage range
Control supply voltage
Rated control supply current
Control input L, R:
Output data
Switching principle
Rated operating voltage U
Operating voltage range
as per UL 508/UL 60947-4-1A/UL 60947-1
Load current at 20°C (see 8.2. Derating curve)
Rated operating current I
AC-51
AC-53a
as per UL 508/UL 60947-4-1A/UL 60947-1
Nominal switching performance
as per UL 508/UL 60947-4-1A/UL 60947-1
Leakage current (input, output)
Residual voltage at I
s
Switching level "Safe off" < 5 V DC
as per IEC 60947-1 ≤ 40 mA
Switching level "Low" -3 ... 9.6 V DC
Switching level "Safe off" < 5 V DC
Switching level "High" 19.2 ... 30 V DC
Input current ≤ mA
as per IEC 60947-1 500 V AC (50/60 Hz)
e
as per IEC 60947-1
as per IEC 60947-1
e
as per IEC 60947-4-3
as per IEC 60947-4-2
Full Load (power factor = 0.4)
Full Load (power factor = 0.8)
e
Order No. ELR H5-IES-SC- 24DC/500AC-0,6 2900582
ELR H5-IES-SC- 24DC/500AC-2
ELR H5-IES-SC- 24DC/500AC-9
ELR H5-IES-SC-230AC/500AC-0,6 2900692
ELR H5-IES-SC-230AC/500AC-2
ELR H5-IES-SC-230AC/500AC-9
ELR...-24DC/...
24 V DC
19.2 ... 30 V DC
(32 V DC, max. 1 min.)
load side ELR...-0.6
Safety end level with bypass, three-phase
electrically isolated switch-off
42...550 V AC
42...500 V AC
0.075...0.6 A
0.6 A
0.6 A
0.6 A
0.3 kW (0.4 HP)
0.5 kW (0.6 HP)
0 mA
< 200 mV
ELR...-230AC/...
230 V AC (50/60 Hz)
85 ... 253 V AC
< 5 V AC
≤4 mA
< 44 V AC
< 5 V AC
85 ... 253 V AC
≤7 mA
ELR...-2
ELR...-9
0.18...2.4 A
1,5... 9.0 A
2.4 A
9 A
2.4 A
6.5 A
2.4 A
6.5 A
0.9 kW (1.2 HP)
2.3 kW (3.0 HP)
1.7 kW (2.2 HP)
4.6 kW (6.1 HP)
0 mA
0 mA
< 300 mV
< 500 mV
2900414
2900421
2900420
2900422
19