TYPE 00 - 01 - 03 ONLY: Adjustment of the closing stroke margin: it adjusts the duration of the last part of
the stroke during which an obstacle is interpreted as a stroke, blocking the motor without performing the
inversion.
For motors with encoders, the set value indicates the number of revolutions of the rotor; while for motors
without encoder, the value is expressed in% of the maximum stroke.
TYPE 02 ONLY: Adjustment of the stop-margin in closing: adjusts the duration of the last part of the closing
movement, in which an obstacle is seen as a stop, causing the motor to stop without reversal on the obstacle.
The value is expressed in number of revolutions of the rotor.
TYPE 00 - 01 - 03 ONLY: Operators force adjustment at stroke arrival - If=0, setting off (the force value on the
stroke is calculated automatically) - If≠0 (operators with encoder) it indicates the force value (expressed in%
of the max value) set in the last length.
TYPE 02 ONLY: Force adjustment in the stop margin in closing, its duration is set through P059.
"Energy saving" mode: If=1 after 10sec of inactivity, the control panel turns the 24V outputs and the display
off that will be turned on at fi rst command received (use recommended battery-powered and / or solar
panel).
Warning: when "Energy saving" is enabled, SAS function is not available.
Warning: when "Energy saving" is enabled, only the stabilized output 24V_ST must be used to power
accessories.
Electric-lock output operating: If=0 "boost" output for electric-lock art.110 power supply, If=1 24V output
controlled by the ELOCK_IN input as pulsed mode,If=2 24V output controlled by the ELOCK_IN input as
step-by-step mode, If=3 electro-brake output for not self-locking operators, If=4 24V output for electric-lock
power supply via an external relay, If=5 24V output for electro-magnets power supply for barriers, If>5 24V
output controlled by the ELOCK_IN input as temporized mode (the set value indicates the switch-off delay in
seconds).
Warning: To adjust the activation/deactivation times in the 000 | 004 | 005 modes, use parameter P064.
Run direction inversion: If=1 automatically reverses the outputs open/close of the operators, avoiding having
to manual change the wiring when installing the operator in an inverted position.
Warning: Changing this parameter you need to change the parameters for the opening and closing limit
switches.
Electric lock duration adjustment
If P062=000|004, adjust the activation time of the LOCK output;
If P062=005, adjust the deactivation time of the LOCK output;
Maintenance Operations-counter: if = 0 reset the counter and disables the intervention request , if>
0 indicates the number of operations (x 500) to be made before the control panel executes a 4 second
additional pre-fl ash to indicate the need of maintenance.
i.g.: If P065 = 050, operations number = 50x500 = 25000 operations
Warning: Before you set a new value of the counter-manoeuvres maintenance, the same must be reset by
setting P065= 0 and only later P065 = "new value".
Selection of operating fl ashing light output: If=0 intermittent fl ashing light output;
If=1 Fixed fl ashing light output (for fl ashing lights with intermittent interior circuits).
EN-26
Operation of the SFT input: if = 0 safety edge always enabled, if = 1 safety edge enabled only
while closing, if = 2 safety edge enabled only while closing and before any movement, if = 3
SAFETY 1
safety edge enabled only when opening, if = 4 safety edge enabled only while opening and
before any movement; as for the obstacle detection with internal anti-crushing sensor, also the
activation of the inputs SFT1 and SFT2 causes the complete or partial reversal as set by P055
SAFETY 2
(duration of inversion on obstacles while opening, and P056 (duration of reversal on obstacle
while closing)