Delay on limit switch detection: the operation is stopped after 1,5 sec from limit switch detection. When
during this delay a stop is detected, the operator is suddenly stopped
Adjustment of acceleration durability
Warning: if soft start is activated, the acceleration is deactivated indipendently from P070 value.
Safeties self-test: if = 0 24V
output with autotest disabled; if = 1 24V
output for safeties with self-test
(it turn the output off and check the contact opening before each maneuver).
Attention: In order to work in self-test mode, all devices must be connected to the stabilized output 24V_ST
(1-2), and be wired and aligned before the motor stroke learning (P003).
Activation of SAS function (with NET_EXP only): SAS output is connected to an input STOP / SAS INPUT of a
second control panel, causing the operation "trap man" (disabling the opening of the second door as long as
the fi rst is not completely closed).
If this parameter is enabled after a reset, it performs an automatic RESP during which the SAS output is not
activated. If limit switches are present and they are crushed after a reset, the RESP is not executed.
Warning: if both doors are manually unlocked and moved from the closed position creates the interlock
condition. You will then need to manually close at least one of the two doors.
Forced "Hold to Run": if this function is enabled, all inputs confi gured as OPEN and CLOSE change
automatically also to OPEN UP and CLOSE UP (hold-to-run commands) if activated and kept active in case a
safety contact (photocell and/or safety edge) is triggered. This function thus allows to control the automation
even in case the safety devices are faulty. If the input is no longer maintained active, the automation returns
to automatic operation.
When using safety edges confi gured as SAFETY 1 or SAFETY 2, this function is not compatible with the values
001 and 003 of parameters P067 and P068.
For security reasons, we recommend that you DO NOT use this function in case there are any clocks/timers
connected to the inputs confi gured as OPEN or CLOSE.
Unused parameter
Unused parameter
Unused parameter
Unused parameter
Confi guration parameters dedicated to the expansion card NET_EXP (for a detailed description of the
parameters, refer to the instruction manual).
EN-28