3.2 Ceiling Bolt Installation Guidelines
1) Wood
The mounting holes for upper foam are used for
auxiliary positioning bolts (if the foam is damaged,
the spacing between the actual lifting lugs shall be
the standard).
Upper foam
Place the wood mounting across the roof beam,
then install the hanging screw bolts.
Wood mounting
Hanging screw bolts
2) New concrete bricks
Inlay or embed the screw bolts.
(Blade shape insertion)
3) Original concrete bricks
Use an embedding screw bolt, crock, and stick
harness.
Embedding screw bolt
(Pipe hanging and embedding screw bolt)
4) Steel roof beam structure
1. Install and use the supporting steel angle.
Hanging screw bolt
Hanging
bolts
CAUTION
The unit body must be completely
aligned with the hole. Ensure that
the unit and the hole are the same
size before moving on.
Installation locating hole
(Middle
pressure)
Roof beam
Ceiling
(Slide insertion)
Steel bar
Supporting
angle steel
2. Install and fit pipes and wires after you have
finished installing the main body.When
choosing where to start, determine the
direction of the pipes to be drawn out.
Especially in cases where there is a ceiling
involved, align the refrigerant pipes, drain
pipes, and indoor and outdoor lines with their
connection points before mounting the unit.
3. Install hanging screw bolts.
Cut off the roof beam.
Strengthen the point at which the cut was
made. Consolidate the roof beam.
4. After you select an installation location,align
the refrigerant pipes, drain pipes, as well as
indoor and outdoor wires with their
connection points before mounting the unit.
5. Drill 4 holes 10cm (4") deep at the ceiling
hook positions in the internal ceiling. Be sure
to hold the drill at a 90° angle to the ceiling.
6. Secure the bolt using the washers and nuts
provided.
7. Install the four suspension bolts.
8. Mount the indoor unit with at least two
people to lift and secure it. Insert suspension
bolts into the unit's hanging holes. Fasten
them using the washers and nuts provided.
9. Mount the indoor unit onto the hanging
screw bolts with a block. Position the indoor
unit flat using a level indicator to prevent
leaks.
Shockproof cushion
Washer
Hanging screw bolt
NOTE:
Confirm the minimum drain
tilt is 1/100 or more.
23
Screw nut
Overhang part
V.1