Branch Circuit Protection
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
For maximum branch circuit protection see table below.
Motor Overload Protection
The devices are provided with load and speed-sensitive overload protection and ther-
mal memory retention upon shutdown or power loss.
The trip current is adjusted to 150% of the rated motor current.
Surrounding Air Temperature Rating
The devices are suitable for an ambient temperature of 40 °C, max. 60 °C with de-ra-
ted output current. To determine the output current rating at temperatures above
40 °C, the output current should be de-rated by 3 % per K between 40 °C and 60 °C.
Wiring Diagrams
For wiring diagrams, refer to chapter "Electrical Installation".
Micro-environmental pollution conditions
For use in pollution degree 1 or 2 micro-environmental conditions only.
SCCR: 65 kA /500 V when protected by
Non-semiconductor fuses
(currents are maximum values)
40 A max./600 V
Inverse time circuit breakers
(currents are maximum values)
40 A max./500 V min.
Instrucciones de funcionamiento – MOVIMOT
Instalación eléctrica
Normas de instalación
®
advanced
5