Installation
Figure 1: Connector (view on connector side)
4.
Installation
4.1.
Safety sensor and actuator
Do not use as a limit stop.
Do not install in strong magnetic fields.
Do not expose to any strong shocks or vibrations.
Keep away from iron filings.
The safety sensor and the accompanying actuators may only be mounted in a volt-
age-free state.
Ensure that all safety sensor and actuator labels are congruently opposed to one
another.
The installation position is arbitrary. The safety sensor and actuator are arranged
according to the figure in the appendix (see actuator operating directions page 67
and 68).
Please note the specified installation tolerances and the approved actuator operat-
ing directions.
The safety sensor is a non-flush mountable proximity sensor (as per EN 60947-5-
2). The safety sensor and actuator must be attached to a non-ferromagnetic mate-
rial so that changes to the operating distances are avoided.
If, however, assembly to a ferromagnetic material is planned, a free zone of 35 mm
(153MSK) or 25 mm (165MSK) is required.
In order to avoid influencing the operating distances, a non-ferromagnetic spacer
with a thickness of at least 10 mm must be used. The above-mentioned free zone
still applies to the sensor and actuator.
Information
24/72
Suitable spacer plates for the sensor and actuator are available from elobau under
order number 350008 (165MSK) and 350009 (153MSK).
www.elobau.com
9010002B01M