DC Inverter U-match Series Floor Ceiling Type Unit
Model
GUHD09NK3FO
GUHD12NK3FO
GUHD18NK3FO
GUHD24NK3FO
GUHD30NK3FO
GUHD36NK3FO
GUHD42NK3FO
GUHD48NK3FO
GUHD36NM3FO
GUHD42NM3FO
GUHD48NM3FO
GUHD60NM3FO
Notes:
The fuse is located on the main board.
① .
Install the disconnect device with a contact gap of at least 3mm in all poles nearby the units
② .
(Both indoor unit and outdoor unit).The appliance must be positioned so that the plug is
accessible.
The specifications of the breaker and power cable listed in the table above are determined
③ .
based on the maximum power (maximum amps) of the unit.
The specifications of the power cable listed in the table above are applied to the conduit-
④ .
guarded multi-wire copper cable (like, YJV copper cable, consisting of PE insulated wires and
a PVC cable jacket) used at 40°С and resistible to 90°С(see IEC 60364-5-52). If the working
condition changes, they should be modified according to the related national standard.
The specifications of the breaker listed in the table above are applied to the breaker with
⑤ .
the working temperature at 40°С. If the working condition changes, they should be modified
according to the related national standard.
Take 2 pieces of power cord of 0.75mm
⑥ .
outdoor unit, with their longest lengths of 50m. Please select the appropriate line length as per
the actual installation conditions. The communication lines can not be twisted together. For
the unit (≤30K), it's recommended to use 8m long communication line.
Take 2 pieces of power cord of 0.75mm
⑦ .
controller and the indoor unit, with their longest lengths of 30m. Please select the appropriate
line length as per the actual installation conditions. The communication lines can not be twisted
together. It's recommended to use 8m long communication line.
The wire size of the communication line should be no less than 0.75mm
⑧ .
2
take 0.75mm
power cords as the communication line.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Table 5
Power
Capability of Air
Supply
Switch(A)
220-240V
~ 50Hz
380-415V 3N
~ 50Hz
2
Minimum Sectional Area of Power
Cable and Earth line (mm
13
13
16
20
20
25
25
40
20
20
25
25
as the communication lines between indoor and
2
as the communication lines between the wired
7
2
)
1.5
1.5
1.5
2.5
2.5
2.5
2.5
6.0
2.5
2.5
2.5
2.5
2
. It's recommended to